T1 - A la pre-opening
• No compressor is running and any compressor in the circuit is
commanded to start (see unit capacity control).
T2 - Pre-open to run
• 5 seconds have elapsed in pre-opening state.
T4 - Pumping down on Off
Any of the following is required:
• Evaporator pressure < Pump downstream pressure value.
•
Unit status = Off
•
Unit status = Off -Quick circuit shutdown alarm active.
T3 - Run to pump down
Any of the following is required:
• Last compressor in the circuit is commanded to stop.
•
Unit status = Pump stopped
• Circuit breaker is open
• Circuit mode is disabled
• Circuit breaker is open -Circuit mode is disabled -Pump down
alarm is active
T5 - Run to Off
Any of the following is required:
•
Unit status = Off
• Fast circuit shutdown alarm is active
• Low temperature start attempt failed
Circuit Functions
Figure 48.
Circuit states.
T6 - Pre-open to Off
Any of the following is required:
•
Unit status = Off
•
Unit status = Pump off
• Circuit breaker is open
• Circuit mode is disabled
• Circuit quick stop alarm is active
• Pumping alarm is activated
COMPRESSOR CONTROL
Compressors should operate only when the circuit is in the
operating or pumping state. They should not operate when the
circuit is in any other state.
Compressor start-up
A compressor must start if it receives a start command from the
unit capacity control logic.
Compressor shutdown
• A compressor must be shut down if any of the following
situations occur:
• The unit’s capacity control logic commands it to shut down.
• A discharge alarm occurs and sequencing requires this
compressor to be the next compressor to shut down.
• The circuit status is pumping and sequencing requires this
compressor to be the next compressor to shut down.
CONTROLLER CALCULATIONS
A minimum time between compressor starts and a minimum time
between compressor stop and compressor start will apply. The
time values are determined by the start timer and stop timer set
points. These cycle timers should not be applied by power cycling
the chiller. This means that if the power is cut off, the cycle timers
should not be active. These timers can be cleared by a setting on
the controller.
CONDENSER FAN CONTROL
The condenser fan control shall start the fans as required
whenever the compressors are running in the circuit (Tandem).
All fans and solenoid valves shall be off when the circuit is in the
off and pre-open state.
The digital outputs of the condenser fans will turn on or off
immediately for condenser stage changes. The outputs of the
capacitor solenoid valves will turn on immediately when a step-up
stage requires the output to turn on, but will have a delay to turn
off during a step-down stage.
This delay is 20 seconds. If the circuit is turned off, the capacitor
solenoid valve outputs will turn off without delay.
0
2
4
6
8
10
12
14
16
18
20
0
25
50
75
100
125
150
175
200
225
250
Ve
nt
ila
do
r
TR
Figure 49. Fan sequence according to capacity
Fa
n
Содержание Clima-Flex CLIC Series
Страница 23: ...iom clic cf eng www clima flex com 23 Dimensions Packaged Units Figure 14 Dimensional configuration 50 RT...
Страница 24: ...iom clic cf eng www clima flex com 24 Dimensions Packaged Units Figure 15 Dimensional configuration 75 RT...
Страница 25: ...iom clic cf eng www clima flex com 25 Dimensions Packaged Units Figure 16 Dimensional configuration 100 RT...
Страница 26: ...iom clic cf eng www clima flex com 26 Dimensions Packaged Units Figure 17 Dimensional configuration 125 RT...
Страница 27: ...iom clic cf eng www clima flex com 27 Dimensions Packaged Units Figure 18 Dimensional configuration 150 RT...
Страница 28: ...iom clic cf eng www clima flex com 28 Dimensions Packaged Units Figure 19 Dimensional configuration 175 RT...
Страница 29: ...iom clic cf eng www clima flex com 29 Dimensions Packaged Units Figure 20 Dimensional configuration 200 RT...
Страница 30: ...iom clic cf eng www clima flex com 30 Dimensions Packaged Units Figure 21 Dimensional configuration 250 RT...
Страница 31: ...iom clic cf eng www clima flex com 31 Dimensions Packaged Units Figure 22 Dimensional configuration 250 RT...
Страница 39: ...iom clic cf eng www clima flex com 39 Electrical Data...
Страница 41: ...iom clic cf eng www clima flex com 41 Electrical Data...
Страница 43: ...iom clic cf eng www clima flex com 43 Electrical Data...
Страница 45: ...iom clic cf eng www clima flex com 45 Electrical Data...
Страница 46: ...iom clic cf eng www clima flex com 46 Electrical Data...
Страница 48: ...iom clic cf eng www clima flex com 48 Electrical Data...
Страница 53: ...iom clic cf eng www clima flex com 53 R454B Electrical Data Figure 38 RS485 communication...
Страница 57: ...iom clic cf eng www clima flex com 57 R454B Electrical Data Figure 44 Fan controller gas leakage sensor...
Страница 77: ...iom clic cf eng www clima flex com 77 Clic R454b Unit This unit use the R454B Refrigerant...
Страница 117: ...iom clic cf eng www clima flex com 117 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 118: ...iom clic cf eng www clima flex com...