The calculations in this section are used in unit-level control logic
or all-circuit control logic.
EVAPORATOR DELTA T
The Delta T of the evaporator water is calculated as the
temperature of the water entering minus that leaving through all
circuits.
PENDING LWT
The slope of LWT is calculated such that the slope represents the
estimated change in LWT is immediately.
RATE OF DECLINE
The slope value calculated above will be a negative value as the
water temperature is falling. The rate of decline is calculated by
inverting the slope value and imitating it to a minimum value of
4°C/sec.
ERROR LWT
The LWT error is calculated as LWT - target LWT.
UNIT CAPACITY
Unit capacity is the Delta T of the unit operating for GPM of water.
Table 16.
Minimum flow rates and corresponding
maximum effective Delta T capacity with variable
flow rate.
Unit Functions
TR
“Number of
compressors”
Capacity
Unit
“Nominal
Nominal
(Nominal
%)”
“Maximum effective
full (°F)
Capacity DT”
25
1
100%
100%
10.0
50
2
100%
96%
10.5
75
3
100%
92%
10.9
100
4
100%
88%
11.3
125
5
100%
85%
11.8
150
6
100%
81%
12.4
175
7
100%
77%
13.0
200
8
100%
73%
13.6
225
9
100%
70%
14.3
250
10
100%
63%
15.9
Refrigerant saturation temperature
The saturated coolant temperature will be calculated from the
pressure sensor readings for each circuit.
Evaporator approach
The evaporator approximation will be calculated for each circuit.
The equation is as follows
Evaporator approximation = LWT - Evaporator saturated
temperature.
Capacitor approach
The capacitor approximation will be calculated for each circuit.
The equation is as follows
Capacitor approximation = Capacitor saturated temperature-
OAT.
Suction reheating
The suction superheat shall be calculated for each circuit using
the following equation:
Suction superheat = Suction temperature - Evaporator saturated
temperature.
Pumping pressure
The pressure at which a circuit will pump down is based on the low
pressure set point of the evaporator. The equation is as follows
Pump down pressure = Evaporator low pressure set point -
103KPA (15 PSI)
CIRCUIT LOGIC CONTROL
Circuit enablement
• A circuit must be enabled to start if the following conditions
are met:
• The circuit breaker is closed
• No circuit alarms are active
• The circuit mode setpoint is set to Enable
• At least one compressor is enabled to start (according to the
enable setpoints)
COMPRESSOR AVAILABILITY
A compressor is considered to be available to start if all of the
following are met:
• The corresponding circuit is enabled.
• The corresponding circuit is not in pump down.
• No cycle timers are active for the compressor.
• The corresponding circuit is not in pumping stop state -No
cycle timers are active for the compressor.
• Compressor is enabled through the enable set points.
• Compressor is not running.
CONTROLLER CALCULATIONS
CIRCUIT STATES
The circuit will always be in one of four states:
Off - The circuit is not running.
Pre-open - The circuit is preparing to start up Running - The
circuit is running
Pump off - The circuit is performing a normal shutdown.
The transitions between these states are shown in the diagram
on the next page.
Содержание Clima-Flex CLIC Series
Страница 23: ...iom clic cf eng www clima flex com 23 Dimensions Packaged Units Figure 14 Dimensional configuration 50 RT...
Страница 24: ...iom clic cf eng www clima flex com 24 Dimensions Packaged Units Figure 15 Dimensional configuration 75 RT...
Страница 25: ...iom clic cf eng www clima flex com 25 Dimensions Packaged Units Figure 16 Dimensional configuration 100 RT...
Страница 26: ...iom clic cf eng www clima flex com 26 Dimensions Packaged Units Figure 17 Dimensional configuration 125 RT...
Страница 27: ...iom clic cf eng www clima flex com 27 Dimensions Packaged Units Figure 18 Dimensional configuration 150 RT...
Страница 28: ...iom clic cf eng www clima flex com 28 Dimensions Packaged Units Figure 19 Dimensional configuration 175 RT...
Страница 29: ...iom clic cf eng www clima flex com 29 Dimensions Packaged Units Figure 20 Dimensional configuration 200 RT...
Страница 30: ...iom clic cf eng www clima flex com 30 Dimensions Packaged Units Figure 21 Dimensional configuration 250 RT...
Страница 31: ...iom clic cf eng www clima flex com 31 Dimensions Packaged Units Figure 22 Dimensional configuration 250 RT...
Страница 39: ...iom clic cf eng www clima flex com 39 Electrical Data...
Страница 41: ...iom clic cf eng www clima flex com 41 Electrical Data...
Страница 43: ...iom clic cf eng www clima flex com 43 Electrical Data...
Страница 45: ...iom clic cf eng www clima flex com 45 Electrical Data...
Страница 46: ...iom clic cf eng www clima flex com 46 Electrical Data...
Страница 48: ...iom clic cf eng www clima flex com 48 Electrical Data...
Страница 53: ...iom clic cf eng www clima flex com 53 R454B Electrical Data Figure 38 RS485 communication...
Страница 57: ...iom clic cf eng www clima flex com 57 R454B Electrical Data Figure 44 Fan controller gas leakage sensor...
Страница 77: ...iom clic cf eng www clima flex com 77 Clic R454b Unit This unit use the R454B Refrigerant...
Страница 117: ...iom clic cf eng www clima flex com 117 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 118: ...iom clic cf eng www clima flex com...