Pre-Start Checklist - Scroll Compressor Chillers
Must be completed, signed, and provided to
Clima Flex
at least 2 weeks prior to requested start date.
Job Name
Installation Location
Customer Order Number
Model Number(s)
G.O. Number(s)
Chilled Water and Condenser Water for Water-cooled Chiller
Yes
No
N/A
Initials
Piping Complete
Water strainer(s) installed in piping per manual requirements
Water System - flushed, filled, and vented; Water treatment in place
Cooling tower flushed, filled, vented; Water treatment in place (if applicable)
Pumps installed and operational (rotation checked, strainers cleaned)
Controls operational (3-way valves, face/bypass dampers, bypass valves, etc.)
Water system operated and tested; flow meets unit design requirements (Not all units include it)
Flow switch(es) -installed, wired, and calibrated
Vent installed on evaporator
Electrical
Yes
No
N/A
Initials
Building controls operational
*Power leads connected to power block or optional disconnect
Power leads have been checked for proper phasing and voltage
All interlock writing complete and compliant with unit specifications
Power applied at least 12 hours before startup
Oil heaters energized at least 12 hours before startup
Chiller components (EXV Sensors Transducers) installed and wired properly
*Wiring complies with National Electrical Code and local codes (See Notes)
Miscellaneous
Yes
No
N/A
Initials
Unit control switches all off
Remote Evaporator / Condenser Piping
factory reviewed
All refrigerant components/piping leak tested, evacuated and charged
Thermometers, wells, gauges, control, etc., installed
Minimum system load of 80% capacity available for testing/ adjusting controls
Document Attached:
Technical Breakdown from Selection Software
Document Attached:
Final Order Acknowledgement
Document Attached:
Remote piping approval
Notes:
The most common problems delaying start-up and affecting unit reliability are:
1. Field installed compressor motor power supply leads too small. Questions: Contact the local Clima Flex sales representative*. State size, number and type of conductors
and conduits installed:
a. From Power supply to chiller __________________________________________________________________
* Refer to NFPA 70-2017, Article 440.35
2. Remote Evaporator piping incomplete or incorrect. Provide approved piping diagrams.
3. Items on this list incorrectly acknowledged resulting in delayed start and possible extra expenses incurred by return trips.
Contactor Representative
Singed
Name
Company
Date
Phone / Email
Clima Flex Sales Representative
Signed
Name
Company
Date
Phone /Email
Содержание Clima-Flex CLIC Series
Страница 23: ...iom clic cf eng www clima flex com 23 Dimensions Packaged Units Figure 14 Dimensional configuration 50 RT...
Страница 24: ...iom clic cf eng www clima flex com 24 Dimensions Packaged Units Figure 15 Dimensional configuration 75 RT...
Страница 25: ...iom clic cf eng www clima flex com 25 Dimensions Packaged Units Figure 16 Dimensional configuration 100 RT...
Страница 26: ...iom clic cf eng www clima flex com 26 Dimensions Packaged Units Figure 17 Dimensional configuration 125 RT...
Страница 27: ...iom clic cf eng www clima flex com 27 Dimensions Packaged Units Figure 18 Dimensional configuration 150 RT...
Страница 28: ...iom clic cf eng www clima flex com 28 Dimensions Packaged Units Figure 19 Dimensional configuration 175 RT...
Страница 29: ...iom clic cf eng www clima flex com 29 Dimensions Packaged Units Figure 20 Dimensional configuration 200 RT...
Страница 30: ...iom clic cf eng www clima flex com 30 Dimensions Packaged Units Figure 21 Dimensional configuration 250 RT...
Страница 31: ...iom clic cf eng www clima flex com 31 Dimensions Packaged Units Figure 22 Dimensional configuration 250 RT...
Страница 39: ...iom clic cf eng www clima flex com 39 Electrical Data...
Страница 41: ...iom clic cf eng www clima flex com 41 Electrical Data...
Страница 43: ...iom clic cf eng www clima flex com 43 Electrical Data...
Страница 45: ...iom clic cf eng www clima flex com 45 Electrical Data...
Страница 46: ...iom clic cf eng www clima flex com 46 Electrical Data...
Страница 48: ...iom clic cf eng www clima flex com 48 Electrical Data...
Страница 53: ...iom clic cf eng www clima flex com 53 R454B Electrical Data Figure 38 RS485 communication...
Страница 57: ...iom clic cf eng www clima flex com 57 R454B Electrical Data Figure 44 Fan controller gas leakage sensor...
Страница 77: ...iom clic cf eng www clima flex com 77 Clic R454b Unit This unit use the R454B Refrigerant...
Страница 117: ...iom clic cf eng www clima flex com 117 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 118: ...iom clic cf eng www clima flex com...