Problem
Possible causes
Possible corrective actions
Compressor oil
level too high or
too low.
Low oil level.
Adjust the water flow required for the equipment.
Insufficient water flow - level too high.
Check or replace (if necessary) the valve and adjust the proper
superheat.
Solenoid valve return oil not open.
Check circuit and possible problem of solenoid valve not opening,
if necessary replace.
Short cycling.
Check pressure drop or temperature for diagnostics.
Excess liquid in crankcase - level too high.
Check means of regulating condenser temperature.
Level too high with compressor operation.
If the system has excess oil, recover and adjust by observing the
sight glass on the compressor.
Operation or selection of expansion value.
Correct power supply.
Compressor mechanical problems.
Check electrical circuit for possible problem. Then replace
compressor.
Incorrect oil for application.
Check all connections and tighten, if necessary replace contactors.
Oil collapse in remote piping.
See corrective steps for high discharge pressure.
Loose fitting in oil line
Correct to bring conditions within allowable limits.
Compressor
staging intervals
too short.
Control band not properly adjusted.
Check and correct.
Water temperature sensor failure.
Set correct superheat.
Insufficient water flow.
Check for possible problem. Then replace the compressor.
Rapid temperature or flow changes.
Check and stabilize load or correct control settings for the
application.
Oversized equipment.
Evaluate equipment selection.
Light loads.
Checking and adjusting the load.
Equipment will
not run.
Inadequate voltage.
Check voltage and correct it.
Reset switch is off.
Power up.
No water flow in the system.
Flush the system.
Water flow is reversed.
Check water direction.
Unit runs, but
does not cool
sufficiently.
Set temperature value is an incorrect
setting.
Set values.
Check data sheet and check system for leaks.
High condensing temperature.
Check condenser and repair.
Equipment does not have sufficient water
flow.
Check technical data, check filter in water line and adjust flow if
necessary.
The fan does not
work.
No supply voltage.
Check electrical circuit (line down).
Motor defective.
Contact the manufacturer.
Motor thermal protection switch open.
Check operating conditions, if necessary contact the manufacturer.
Troubleshooting Chart
Содержание Clima-Flex CLIC Series
Страница 23: ...iom clic cf eng www clima flex com 23 Dimensions Packaged Units Figure 14 Dimensional configuration 50 RT...
Страница 24: ...iom clic cf eng www clima flex com 24 Dimensions Packaged Units Figure 15 Dimensional configuration 75 RT...
Страница 25: ...iom clic cf eng www clima flex com 25 Dimensions Packaged Units Figure 16 Dimensional configuration 100 RT...
Страница 26: ...iom clic cf eng www clima flex com 26 Dimensions Packaged Units Figure 17 Dimensional configuration 125 RT...
Страница 27: ...iom clic cf eng www clima flex com 27 Dimensions Packaged Units Figure 18 Dimensional configuration 150 RT...
Страница 28: ...iom clic cf eng www clima flex com 28 Dimensions Packaged Units Figure 19 Dimensional configuration 175 RT...
Страница 29: ...iom clic cf eng www clima flex com 29 Dimensions Packaged Units Figure 20 Dimensional configuration 200 RT...
Страница 30: ...iom clic cf eng www clima flex com 30 Dimensions Packaged Units Figure 21 Dimensional configuration 250 RT...
Страница 31: ...iom clic cf eng www clima flex com 31 Dimensions Packaged Units Figure 22 Dimensional configuration 250 RT...
Страница 39: ...iom clic cf eng www clima flex com 39 Electrical Data...
Страница 41: ...iom clic cf eng www clima flex com 41 Electrical Data...
Страница 43: ...iom clic cf eng www clima flex com 43 Electrical Data...
Страница 45: ...iom clic cf eng www clima flex com 45 Electrical Data...
Страница 46: ...iom clic cf eng www clima flex com 46 Electrical Data...
Страница 48: ...iom clic cf eng www clima flex com 48 Electrical Data...
Страница 53: ...iom clic cf eng www clima flex com 53 R454B Electrical Data Figure 38 RS485 communication...
Страница 57: ...iom clic cf eng www clima flex com 57 R454B Electrical Data Figure 44 Fan controller gas leakage sensor...
Страница 77: ...iom clic cf eng www clima flex com 77 Clic R454b Unit This unit use the R454B Refrigerant...
Страница 117: ...iom clic cf eng www clima flex com 117 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 118: ...iom clic cf eng www clima flex com...