4/13
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
4.A
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
4.B
[9-04]
R/W
1~4°C, step: 1°C
2°C
4.C
[2-06]
R/W
0: Disabled
1: Enabled
Tank
5.2
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
55°C
5.3
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.4
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.6
[6-0D]
R/W
0: Reheat only
3 scheduled reheat
└─
Disinfection
5.7.1
[2-01]
R/W
0: No
1: Yes
5.7.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
5.7.3
[2-02]
R/W
0~23 hour, step: 1 hour
1
5.7.4
[2-03]
R/W
60°C
60°C
5.7.5
[2-04]
R/W
40~60 min, step: 5 min
40 min
Tank
5.8
[6-0E]
R/W
[E-07]=4
40~75°C, step: 1°C
60°C
5.9
[6-00]
R/W
2~40°C, step: 1°C
8°C
5.A
[6-08]
R/W
2~20°C, step: 1°C
10°C
5.B
R/W
0: Fixed
1: Weather dependent
└─
WD curve
5.C
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
50°C
5.C
[0-0C]
R/W
Min(45~[6-0E])
~
[6-0E]°C, step: 1°C
55°C
5.C
[0-0D]
R/W
10~25°C, step: 1°C
15°C
5.C
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
Tank
5.D
[6-01]
R/W
0~10°C, step: 1°C
0°C
5.E
R/O
0: 2-points
1: Slope-Offset
User settings
└─
Quiet
7.4.1
R/W
0: OFF
1: Manual
2: Automatic
7.4.3
R/W
0: Quiet
1: More Quiet
2: Most Quiet
└─
Electricity price
7.5.1
R/W
0,00~990/kWh
1/kWh
7.5.2
R/W
0,00~990/kWh
1/kWh
7.5.3
R/W
0,00~990/kWh
1/kWh
User settings
7.6
R/W
0,00~990/kWh
0,00~290/MBtu
1,0/kWh
Installer settings
└─
Configuration wizard
└─
System
9.1.3.2
[E-03]
R/O
(*6,*7,*8)
R/W (*9)
0: no heater (*9)
2: 3V (*6)
3: 6V (*7)
4: 9W (*8)
9.1.3.3
[E-05]
[E-06]
[E-07]
R/O
HPSU 'Integrated'
9.1.3.4
[4-06]
R/W
0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
9.1.3.5
[7-02]
R/W
0: Single zone
1: Dual zone
9.1.3.6
[E-0D]
R/W
0: No
1: Yes
9.1.3.7
[6-02]
R/W
0~10kW, step: 0,2kW
0kW
BSH capacity
Gas price
BUH type
Domestic hot water
Emergency
Number of zones
Glycol filled system
WD curve type
Activation
Level
High
Medium
Low
Setpoint mode
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Margin
Start time
Tank setpoint
Duration
Maximum
Hysteresis
Reheat hysteresis
Comfort setpoint
Eco setpoint
Reheat setpoint
Heat up mode
Activation
Operation day
Increase around 0°C
Overshoot
Antifrost
4P670988-1 - 2021.09
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*6) EKECBUA3V_(*7) EKECBUA6V_(*8) EKECBUA9W_(*9) BUH less_
(*10) 11P_(*11) 16P