11
|
Configuration
Installer reference guide
159
ERLA11~W1 + EBSH/X(B)11+16P30+50DF
Daikin Altherma 3 R ECH₂O
4P663482-1A – 2021.11
6
Press the left dial to confirm the new setting.
7
Press the center button to go back to the home screen.
INFORMATION
When you change the overview settings and you go back to the home screen, the
user interface will show a popup screen and request to restart the system.
When confirmed, the system will restart and recent changes will be applied.
11.1.2 To connect the PC cable to the switch box
This connection between PC and hydro PCB is needed when updating the hydro
software and EEPROM.
Prerequisite:
The EKPCCAB4 kit is required.
1
Connect the USB connector of the cable to your PC.
2
Connect the plug of the cable to X10A on A1P of the switch box of the indoor
unit.
A1P
X10A
3
Pay special attention to the position of the plug!
2
3
4
5
H J
ST
11.2 Configuration wizard
After first power ON of the system, the user interface will guide you using the
configuration wizard. This way you can set the most important initial settings. This
way the unit will be able to run properly. Afterwards, more detailed settings can be
done via the menu structure if required.
You can find a short overview of the settings in the configuration here. All the
settings can also be adjusted in the settings menu (use the breadcrumbs).