16
|
Disposal
Installer reference guide
280
ERLA11~W1 + EBSH/X(B)11+16P30+50DF
Daikin Altherma 3 R ECH₂O
4P663482-1A – 2021.11
16.1.4 Recovery mode — In case of 1N~ models (7-LEDs display)
Before recovering refrigerant, make sure the electronic expansion valves are open.
When power is ON, this has to be done by using the recovery mode.
Components
To activate/deactivate the recovery mode, you need the following components:
BS2
SET
BS1
MODE
BS3
RETURN
BS4
PUMP DOWN
H1P
H2P
H3P
H4P
H5P
H6P
H7P
DEMAND
L.N.O.P.
HWL
MODE
TEST
1N~
H1P~H7P
7‑LEDs display
BS1~BS4
Push buttons. Operate the push buttons with an insulated stick (such as a closed
ballpoint pen) to avoid touching of live parts.
1N~
BS2
SET
BS1
MODE
BS3
RETURN
BS4
PUMP DOWN
H1P
H2P
H3P
H4P
H5P
H6P
H7P
DEMAND
L.N.O.P.
HWL
MODE
TEST
H1P~H7P
7‑LEDs display
BS1~BS4
Push buttons. Operate the push buttons with an insulated stick (such as a closed
ballpoint pen) to avoid touching of live parts.
To activate the recovery mode
INFORMATION
If you get confused in the middle of the process, press BS1 to return to the default
situation.
Before recovering refrigerant, activate the recovery mode as follows: