Field Settings
Part 7 Trial Operation and Field Settings
265
Note(s)
5.2.2 Overview of Field Settings for FFQ Series
Factory Setting
Any function that is not available on the indoor unit us not displayed.
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01
02
03
04
05
06
10
(20)
0
Filter cleaning
sign interval
Longlife filter
Li
g
ht
Approx.
2,500 hrs.
He
avy
Approx.
1,250 hrs.
—
—
—
—
2
Remote controller thermistor
Enabled
Disabled
—
—
—
—
3
Filter cleaning sign
Display
No display
—
—
—
—
12
(22)
0
Optional accessories output
selection (field selection of
output for adaptor for wiring)
Compressor
—
Operation
output
Error
output
Outdoor
air
intake
Presence
sensor
13
(23)
0
High air outlet velocity (for
high ceiling applications)
≤ 2.7 m
(≤ 8-7/8 ft)
2.7 ~ 3.0 m
(8-7/8~9-13/16 ft)
3.0 ~ 3.5 m
(9-13/16~11-1/2 ft)
—
—
—
1
Selection of airflow direction
(setting for when a blocking
pad kit has been installed)
4-way flow
3-way flow
2-way flow
—
—
—
4
Airflow direction range setting
Upper
Normal
Lower
—
—
—
15
(25)
3
Drain pump operation with
humidifying
Not equipped
Equipped
—
—
—
—
Содержание 4MXL-T Series
Страница 107: ...SiUS121827E SA Indoor Unit Functions Part 4 Functions and Control 101 FFQ Series Emergency operation switch R24077 ...
Страница 182: ...Troubleshooting for RA Indoor Unit SiUS121827E 176 Part 6 Service Diagnosis Reference Check No 11 Refer to P 235 ...
Страница 190: ...Troubleshooting for SA Indoor Unit SiUS121827E 184 Part 6 Service Diagnosis Reference Check No 02 Refer to P 233 ...
Страница 249: ...SiUS121827E Check Part 6 Service Diagnosis 243 R6000583 1 2 3 4 Multimeter Front side Rear side ...
Страница 288: ...Piping Diagrams SiUS121827E 282 Part 8 Appendix 1 2 Outdoor Unit 5MXS48TVJU 4MXL36TVJU 3D117817 3D118311 ...
Страница 298: ...Operation Limit SiUS121827E 292 Part 8 Appendix 4 Operation Limit 5MXS48TVJU 4MXL36TVJU 3D048149D 3D101428 ...