SiUS121827E
RA Indoor Unit Functions
Part 4 Functions and Control
67
FDXS, CDXS, FVXS Series
Ex: When the target temperature is 25°C (77°F)
Cooling → 23°C (73.4°F): Thermostat OFF → 22°C (71.6°F): Switch to heating
Heating → 26.5°C (79.7°F): Thermostat OFF → 27.5°C (81.5°F): Switch to cooling
2.5 Thermostat Control
Outline
Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Details
Thermostat OFF Conditions
The temperature difference is in the zone A.
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling: 10 minutes, Heating: 10 seconds)
Cooling
Heating
FTXR, CTXG Series
Target tempe 2.5°C (+4.5°F)
Heating Operation
Target temperature – 3.0°C (–5.4°F)
Cooling Operation
(R22000)
Target temperature – 2.0°C (–3.6°F)
= Thermostat OFF
Target tempe 1.5°C (+2.7°F)
= Thermostat OFF
Zone B
Zone B
Zone A
Zone A
OFF
OFF
ON
ON
Zone C
Zone C
Room thermistor temperature – target temperature
–1.0°C (–1.8°F)
–2.0°C (–3.6°F)
(R24031)
–0.5°C (–0.9°F)
–1.5°C (–2.7°F)
Zone B
Zone B
Zone A
Zone A
OFF
OFF
ON
ON
Zone C
Zone C
1.5°C (2.7°F)
0.5°C (0.9°F)
0°C (0°F)
1.0°C (1.8°F)
Room thermistor temperature – target temperature
(R24032)
Содержание 4MXL-T Series
Страница 107: ...SiUS121827E SA Indoor Unit Functions Part 4 Functions and Control 101 FFQ Series Emergency operation switch R24077 ...
Страница 182: ...Troubleshooting for RA Indoor Unit SiUS121827E 176 Part 6 Service Diagnosis Reference Check No 11 Refer to P 235 ...
Страница 190: ...Troubleshooting for SA Indoor Unit SiUS121827E 184 Part 6 Service Diagnosis Reference Check No 02 Refer to P 233 ...
Страница 249: ...SiUS121827E Check Part 6 Service Diagnosis 243 R6000583 1 2 3 4 Multimeter Front side Rear side ...
Страница 288: ...Piping Diagrams SiUS121827E 282 Part 8 Appendix 1 2 Outdoor Unit 5MXS48TVJU 4MXL36TVJU 3D117817 3D118311 ...
Страница 298: ...Operation Limit SiUS121827E 292 Part 8 Appendix 4 Operation Limit 5MXS48TVJU 4MXL36TVJU 3D048149D 3D101428 ...