SiUS121827E
SA Indoor Unit Functions
Part 4 Functions and Control
97
3.9 Presence and Floor Sensors (Option)
Applicable
Models
FFQ09/12/15/18Q2VJU
Outline
With the human presence signal and the floor temperature signal from the optional sensor kit, the
system provides the energy saving control, or the comfortable temperature control and airflow
direction control preventing the direct draft to the human.
To use sensor related functions, a wired remote controller (BRC1E73) and optional sensor kit
(BRYQ60A2W(S)) are necessary to be installed.
Details
1. Draft prevention (with presence sensor)
When the sensor detects human presence during auto-swing operation, the system sets the airflow
direction parallel to the floor (position 0) to reduce unpleasant draft.
The operation returns to the normal auto-swing as the sensor detects no human in the room.
Draft prevention is enabled only when decoration panel BYFQ60C2W1W(S), sensor kit
BRYQ60A2W(S) and wired remote controller BRC1E73 are connected to the main unit and
draft prevention is set to “enabled” on the wired remote controller.
Factory setting is “disabled”.
Draft prevention cannot be activated when individual flap control is set, even if draft prevention
is enabled on the wired remote controller.
Setting on the wired remote controller
R4003392
1
Setting
Main Menu
Configuration
Current Settings
Clock & Calendar
2/3
2
Draft Prevention
Configuration
Setting
3
Enable
Draft Prevention
Enable/Disable
Setting
4
No
Yes
Draft Prevention
Save the settings?
Setting
Press
Menu/OK
button to display the
main menu screen.
Press buttons to select
Yes
.
The confirmation screen will appear
when
Menu/OK
button is pressed.
Press
Menu/OK
button to confirm the
settings and to return to the basic
screen.
Language
Contrast Adjustment
Display
Press buttons to select
Configuration
and press
Menu/OK
button.
Press buttons to select
Draft Prevention
and press
Menu/OK
button.
Press buttons to select
Enable
.
Содержание 4MXL-T Series
Страница 107: ...SiUS121827E SA Indoor Unit Functions Part 4 Functions and Control 101 FFQ Series Emergency operation switch R24077 ...
Страница 182: ...Troubleshooting for RA Indoor Unit SiUS121827E 176 Part 6 Service Diagnosis Reference Check No 11 Refer to P 235 ...
Страница 190: ...Troubleshooting for SA Indoor Unit SiUS121827E 184 Part 6 Service Diagnosis Reference Check No 02 Refer to P 233 ...
Страница 249: ...SiUS121827E Check Part 6 Service Diagnosis 243 R6000583 1 2 3 4 Multimeter Front side Rear side ...
Страница 288: ...Piping Diagrams SiUS121827E 282 Part 8 Appendix 1 2 Outdoor Unit 5MXS48TVJU 4MXL36TVJU 3D117817 3D118311 ...
Страница 298: ...Operation Limit SiUS121827E 292 Part 8 Appendix 4 Operation Limit 5MXS48TVJU 4MXL36TVJU 3D048149D 3D101428 ...