SiUS121827E
Field Settings
Part 7 Trial Operation and Field Settings
261
Reference
5.1.4 Jumper and Switch Settings
FTXR series
CTXG, CTXS, FTXS, FDXS, CDXS, FVXS series
FVXS series only
For the location of the jumper, refer to the following pages.
FTXR, CTXG: page 37
CTXS07LVJU, FTXS09/12LVJU: page 39
FTXS15/18/24LVJU: page 41
FDXS, CDXS: page 43
FVXS: page 45
Jumper
on indoor
unit PCB
Function
When connected
(factory setting)
When cut
JB
Fan speed setting when
compressor stops for
thermostat OFF.
(effective only at cooling
operation)
The fan stops.
Fan speed setting;
Remote controller setting
JC
Power failure recovery
function
Auto-restart
The unit does not
resume operation after
recovering from a power
failure. Timer settings
are cleared.
Jumper
on indoor
unit PCB
Function
When connected
(factory setting)
When cut
JB
Fan speed setting when
compressor stops for
thermostat OFF.
(effective only at cooling
operation)
Fan speed setting;
Remote controller setting
The fan stops.
JC
Power failure recovery
function
Auto-restart
The unit does not
resume operation after
recovering from a power
failure. Timer settings
are cleared.
Switch
on indoor unit
PCB
Function
OFF
(factory setting)
ON
SW2-4
Upward airflow limit
setting
Exposed or half
embedded installation
Set the switch to ON
position when you install
the indoor unit
embedded in the wall to
avoid condensation.
Содержание 4MXL-T Series
Страница 107: ...SiUS121827E SA Indoor Unit Functions Part 4 Functions and Control 101 FFQ Series Emergency operation switch R24077 ...
Страница 182: ...Troubleshooting for RA Indoor Unit SiUS121827E 176 Part 6 Service Diagnosis Reference Check No 11 Refer to P 235 ...
Страница 190: ...Troubleshooting for SA Indoor Unit SiUS121827E 184 Part 6 Service Diagnosis Reference Check No 02 Refer to P 233 ...
Страница 249: ...SiUS121827E Check Part 6 Service Diagnosis 243 R6000583 1 2 3 4 Multimeter Front side Rear side ...
Страница 288: ...Piping Diagrams SiUS121827E 282 Part 8 Appendix 1 2 Outdoor Unit 5MXS48TVJU 4MXL36TVJU 3D117817 3D118311 ...
Страница 298: ...Operation Limit SiUS121827E 292 Part 8 Appendix 4 Operation Limit 5MXS48TVJU 4MXL36TVJU 3D048149D 3D101428 ...