Field Settings
SiUS121827E
266
Part 7 Trial Operation and Field Settings
Note(s)
5.2.3 Overview of Field Settings for FDMQ Series
Factory Setting
The Second Code No. is factory set to "01".
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial settings for all the indoor units of the
group are equal.
For group control, refer to the installation manual attached to the indoor unit for group control.
External Static Pressure Settings
Factory Setting
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01
02
03
04
05
06
10
(20)
0
Filter cleaning
sign interval
(used to change
filter cleaning
display interval
according to filter
contamination)
Longlife
filter
Lig
ht
Approx.
2,500
hrs.
Heavy
Approx.
1,250
hrs.
—
—
—
—
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
—
—
—
—
3
Filter cleaning sign (used to
set filter cleaning display ON/
OFF)
Display
No display
—
—
—
—
11
(21)
7
Air volume adjustment
OFF
Air volume
adjustment
completion
Air volume
adjustment
start
—
—
—
13
(23)
6
External static pressure
Refer to the table below.
Mode
No.
First
Code
No.
Second Code No.
External static pressure
09/12
Class
15/18/24
Class
13
(23)
6
03
—
30 Pa (0.12 inH
2
O)
04
—
40 Pa (0.16 inH
2
O)
05
05
50 Pa (0.20 inH
2
O)
06
06
60 Pa (0.24 inH
2
O)
07
07
70 Pa (0.28 inH
2
O)
08
08
80 Pa (0.32 inH
2
O)
09
09
90 Pa (0.36 inH
2
O)
10
10
100 Pa (0.40 inH
2
O)
11
11
110 Pa (0.44 inH
2
O)
12
12
120 Pa (0.48 inH
2
O)
13
13
130 Pa (0.52 inH
2
O)
14
14
140 Pa (0.56 inH
2
O)
15
15
150 Pa (0.60 inH
2
O)
Содержание 4MXL-T Series
Страница 107: ...SiUS121827E SA Indoor Unit Functions Part 4 Functions and Control 101 FFQ Series Emergency operation switch R24077 ...
Страница 182: ...Troubleshooting for RA Indoor Unit SiUS121827E 176 Part 6 Service Diagnosis Reference Check No 11 Refer to P 235 ...
Страница 190: ...Troubleshooting for SA Indoor Unit SiUS121827E 184 Part 6 Service Diagnosis Reference Check No 02 Refer to P 233 ...
Страница 249: ...SiUS121827E Check Part 6 Service Diagnosis 243 R6000583 1 2 3 4 Multimeter Front side Rear side ...
Страница 288: ...Piping Diagrams SiUS121827E 282 Part 8 Appendix 1 2 Outdoor Unit 5MXS48TVJU 4MXL36TVJU 3D117817 3D118311 ...
Страница 298: ...Operation Limit SiUS121827E 292 Part 8 Appendix 4 Operation Limit 5MXS48TVJU 4MXL36TVJU 3D048149D 3D101428 ...