SiUS121827E
SA Indoor Unit Functions
Part 4 Functions and Control
93
Enabling or disabling the schedule
3.6 Setback Function (With Wired Remote Controller
BRC1E73)
Applicable
Models
FFQ09/12/15/18Q2VJU
Outline
The Setback function can be used to maintain the space temperature in an assigned range for an
unoccupied period.
Details
The setback icon flashes on the LCD of wired remote controller when the unit is turned on by the
setback control.
When enabled, the Setback mode becomes active when the indoor unit is turned off by either
the user, a schedule event or an off timer.
Setback function is not available by default. It can be enabled by the system installer.
1
2
3
Display the schedule screen.
Press buttons to select
Enable / Disable
on the schedule
screen.
Press
Menu/OK
button to display the
enable/disable screen.
Press buttons to select
Enable
or
Disable
on the enable/disable
screen.
Press
Menu/OK
button after selecting
the item. The confirmation screen is
displayed.
Press buttons to select
Yes
on the
confirmation screen.
Pressing
Menu/OK
button confirms the
enable/disable setting for the schedule
and takes you back to the basic screen.
(R24076)
Содержание 4MXL-T Series
Страница 107: ...SiUS121827E SA Indoor Unit Functions Part 4 Functions and Control 101 FFQ Series Emergency operation switch R24077 ...
Страница 182: ...Troubleshooting for RA Indoor Unit SiUS121827E 176 Part 6 Service Diagnosis Reference Check No 11 Refer to P 235 ...
Страница 190: ...Troubleshooting for SA Indoor Unit SiUS121827E 184 Part 6 Service Diagnosis Reference Check No 02 Refer to P 233 ...
Страница 249: ...SiUS121827E Check Part 6 Service Diagnosis 243 R6000583 1 2 3 4 Multimeter Front side Rear side ...
Страница 288: ...Piping Diagrams SiUS121827E 282 Part 8 Appendix 1 2 Outdoor Unit 5MXS48TVJU 4MXL36TVJU 3D117817 3D118311 ...
Страница 298: ...Operation Limit SiUS121827E 292 Part 8 Appendix 4 Operation Limit 5MXS48TVJU 4MXL36TVJU 3D048149D 3D101428 ...