SiUS121827E
Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis
195
7. Troubleshooting for Outdoor Unit
7.1 Refrigerant Shortage
Error Code
U0
Outdoor Unit LED
Display
A
j
1
h
2
h
3
i
4
i
5
h
Method of Error
Detection
Refrigerant shortage is detected by checking the input current value and the compressor running
frequency. If there is insufficient refrigerant, the input current tends to be lower than the normal
value.
Error Decision
Conditions
The following conditions continue for 7 minutes.
Input current
≤
A
× output fre
B
Output frequency >
C
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
The installation space not large enough
Dirty outdoor heat exchanger
Defective outdoor fan motor
Disconnection of the discharge pipe thermistor, indoor or outdoor heat exchanger thermistor,
room or outdoor temperature thermistor
Closed stop valve
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Defective electronic expansion valve
A
(coefficient)
B
(A)
C
(Hz)
2500/256
50
40
Содержание 4MXL-T Series
Страница 107: ...SiUS121827E SA Indoor Unit Functions Part 4 Functions and Control 101 FFQ Series Emergency operation switch R24077 ...
Страница 182: ...Troubleshooting for RA Indoor Unit SiUS121827E 176 Part 6 Service Diagnosis Reference Check No 11 Refer to P 235 ...
Страница 190: ...Troubleshooting for SA Indoor Unit SiUS121827E 184 Part 6 Service Diagnosis Reference Check No 02 Refer to P 233 ...
Страница 249: ...SiUS121827E Check Part 6 Service Diagnosis 243 R6000583 1 2 3 4 Multimeter Front side Rear side ...
Страница 288: ...Piping Diagrams SiUS121827E 282 Part 8 Appendix 1 2 Outdoor Unit 5MXS48TVJU 4MXL36TVJU 3D117817 3D118311 ...
Страница 298: ...Operation Limit SiUS121827E 292 Part 8 Appendix 4 Operation Limit 5MXS48TVJU 4MXL36TVJU 3D048149D 3D101428 ...