SQLC-220-086
68
Item
Specification
Alarm output
(
27
)
Alarm factor:Demand current, Demand active power, harmonic 5th conversion content,
Harmonic nth content, Distortion factor, Voltage, Alarm OFF.
Possible to setting one of them.
Reset form :Automatic reset or Manual reset (Setting)
Output contact :No voltage normally open contact (a contact) (OR of each phase detection)
Contact capacity:AC250V 8A, DC125V 0.3A (Resistance load) AC250V 2A, DC125V 0.1A (Inductive load)
Alarm factor
Item
Specification
Demand current,
Demand active
power
Function
Demand measurement value ≧ Upper limit setting value,
Alarm display, Alarm output.
Setting accuracy ±1.0% (% for full scale )
Setting range
5 to 100% to the maximum scale. (1% step)
Harmonic 5th
conversion
content
Harmonic nth
content
Distortion
factor
Function
Measurement value ≧ Upper limit setting value,
Alarm display, Alarm output. (Detects by the maximum phase)
Setting accuracy Current:±2.5%, Voltage:±1.0%, % to 100% of content rate.
Setting range
Current
Harmonic 5th conversion content, Harmonic nth content
(n=3,4,5,7,9,11,13,15), Distortion factor
5 to 100% (1% step)
Voltage
Harmonic 5th conversion content, Harmonic nth content
(n=3,4,5,7,9,11,13,15), Distortion factor
1.0to 20.0% (0.1% step)
Detection
characteristics
Average value mode:If the average measured value exceeds the above
setting, it will be detected.
Inverse time delay mode:Detected by the inverse time characteristic
of the instantaneous value (Only 5th harmonic conversion content
rate is possible)
Voltage
Function
Measurement value ≧ Upper limit setting value,
Alarm display, Alarm output. (Detects by the maximum phase)
Measurement value ≦ Lower limit setting value,
Alarm display, Alarm output. (Detects by the minimum phase)
Setting accuracy ±1.0% (% for full scale)
Setting range
Using a full scale as 150%. 30 to 150% (1% step)
CPU error
output
(
27
)
Detection item (Self diagnostics item)
Contact composition
Contact capacity
(1) Watchdog timer
(2) RAM check error
(3) A/D conversion error
At the case of error detection and not applying for
auxiliary supply, an output is ON.
It becomes OR output of a detection item.
Normally close
contact
(b contact)
AC250V 5A, DC125V 0.2A
(Resistance load)
AC250V 1.5A, DC125V 0.1A
(Inductive load)
External
operation
input
Number of circuits 2 circuits, A function (four types) is changed by setting.
Function
Four types of following functions can be operated by adding a voltage signal
from the outside in addition to switch operation.
Alarm reset
Alarm output is reset (output OFF).
Maximum / Minimum
value reset
The maximum/minimum value is reset (it updates to the instantaneous value at
the time).
Measurement
factor change
The measurement display element of the main monitoring is changed.
Phase change
Phase/line display of all the current/voltage currently displayed is changed.
Minimum operation
pulse width
300ms ,Continuation applying is possible.
Rated input
Input rating becomes the same as that of auxiliary supply.
(1) AC100/110V 0.4VA,AC200/220V 1.4VA,DC100/110V 0.4W AC DC two ways.
Contact capacity:About 3mA (AC,DC100/110V) ,About 6mA (AC200/220V)
(2) DC24V 0.3W,DC48V 1.2W
Contact capacity : About 10mA (DC24V) ,About 20mA (DC48V)
Note(
27
) 2 outputs combination is possible, for pulse output and alarm output and
CPU error output. (CPU error output is 1 point only)
Caution on the use of external display selection input (option)
External power consumption is 0.4VA at AC110V or 1.4VA at AC220V or 0.4W at DC110V.
In case a relay or a switch is used for power supply, please use the thing with about
1mA of minimum application loads.