SQLC-220-086
58
(2) 321 to 322 Measurement setting
Set the dead band of measurement display, and with or without of tidal current measurement.
321
Dead band of measurement
RESET/
SHIFT
RESET/SHIFT
322
Tidal current measurement
◆ 321 Measurement dead band
Set the dead band of measurement display.
By this setting, variation of less than this set value is
disregarded by voltage, current, active power, and reactive
power measurement display.
Setting range:0.0 to 2.0% (0.1% step)
Selection by + and - , set value is updated by SET .
Default setting:0.0% (None)
◆ 322 Tidal current measurement
By measurement of reactive power and a power factor,
0 (general measurement) or 1 (tidal current measurement
which was conscious of power transmission / power
receiving) can be selected.
Selection by + and - , set value is updated by SET .
Default setting:0 (General measurement)
General measurement:Displays the polarity (LAG / LEAD) supplied from the power system side.
(Both power receiving and power transmission)
Tidal current measurement:Displays the polarity (LAG / LEAD) supplied from the power system side.
(At power receiving)
Displays the polarity (LAG / LEAD) supplied from the power generation side.
(At power transmission)
Image of reactive power and power factor display
General measurement Tidal current measurement
<Note> When used in a place where power transmission operation is performed (supply from the power generation side
to the power system side), the polarity (LEAD / LAG) of reactive power and power factor measurement during
power transmission changes depending on the power flow measurement setting.
However, the meter display is LEAD on the left and LAG on the right.
0:
General
measurement
+
-
1:
Tidal current
measurement
-
+
Multimeter
Current
direction
Reactive
power
CT
LAG
LEAD
Current
direction
Multimeter
Reactive
power
CT
LAG
LEAD
0°
90°
180°
270°
LAG
LEAD
LAG
LEAD
Voltage standard
Power receiving (Power purchase)
Current of
leading phase
Power transmission
(Power selling)
Polarity seen from the power transmission
side during power transmission (-W)
Polarity
supplied from
the power
system side
Current of
leading phase
Current of
laging phase
Polarity
supplied from
the power
generation side
0°
90°
180°
270°
LAG
LEAD
LEAD
LAG
Voltage standard
Power receiving (Power purchase)
Current of
laging phase
Current of
leading phase
Power transmission
(Power selling)
Polarity as seen from the power receiving
side during power transmission (-W)
Polarity
supplied
from the
power
system side
Power
transmission
Power
receiving
Current of
laging phase
Dead band of measurement
New setting
Current setting
Setting No.
Setting factor
Tidal current measurement
New setting
Current setting
Setting No.