SQLC-220-086
28
Setting mode 3. Function table
Setting
No.
Function
Functional description
Current
input
Default setting
Important
setting
Page
311
Input circuit phase
line change
2VT・3CT product is 3-phase 3-wire
(3φ3W) fixation.
○
3φ3W (Fixed)
○
57
312
Input voltage
Set the input voltage.
110V
○
57
321
Measurement dead
band
Set the dead band of measurement display.
○
0.0%
58
322
Tidal current
measurement
Set the general measurement or tidal
current measurement which was conscious
of power transmission / power receiving,
in measurement of reactive power and
power factor.
General measurement
58
331
(
14
)(
15
)
Analog output
specification
Set the analog output specification.
○
DC1 to 5V or
DC0 to 5V
(Designation )
60
341
(
14
)
AO1 BIAS adjustment
Set the BIAS value of AO1 (Analog output
1).
○
0.0%
60
342
(
14
)
AO1 SPAN adjustment
Set the SPAN value of AO1 (Analog output
1).
○
100.0%
60
343
(
14
)
AO2 BIAS adjustment
Set the BIAS value of AO2 (Analog output
2).
○
0.0%
60
344
(
14
)
AO2 SPAN adjustment
Set the SPAN value of AO2 (Analog output
2).
○
100.0%
60
345
(
14
)
AO3 BIAS adjustment
Set the BIAS value of AO3 (Analog output
3).
○
0.0%
60
346
(
14
)
AO3 SPAN adjustment
Set the SPAN value of AO3 (Analog output
3).
○
100.0%
60
347
(
14
)
AO4 BIAS adjustment
Set the BIAS value of AO4 (Analog output
4).
○
0.0%
60
348
(
14
)
AO4 SPAN adjustment
Set the SPAN value of AO4 (Analog output
4).
○
100.0%
60
Note(
14
) Setting item is not displayed in case there is no corresponding option.
Note(
15
) Setting item is not displayed if analog output is not DC0 to 5V (or DC1 to 5V) specification,
And analog output insulation product does not display a setting item.