SQLC-220-086
21
4.3.7 Reset
Various kinds of reset are performed. The kind of reset is as follows and operations are different, respectively.
Reset of watt-hour integrated value (zero clear),
Reset of maximum value and minimum value (it updates to the instantaneous value at the time),
Alarm output reset (OFF of an alarm output (at the case of manual reset setting)).
And, the operation from each measurement display constitutes conditions at each reset.
(1) Watt-hour integrated value reset
The integrated value of various watt-hour is reset collectively. In detail explanation in the setting mode 2,
please refer to "5.3.2 Setting mode 2".
① Press SET and RESET/SHIFT together for longer than 3 seconds. It goes into the setting mode 2.
② MODE is pushed until setting is set to No.271. Further RESET/SHIFT is pushed once and it is made a watt-hour
reset display.
③ Press SET for longer than 3 seconds.
④ DISPLAY is pushed and it returns to a measurement display.
Measurement display
No.211
No.272(Clear completion) No.272(Before clear)
Setting mode 2
DISPLAY
SET + RESET/SHIFT
3 seconds
New setting
RESET/SHIFT
MODE
×n
(To setting No.272)
Setting No.
SET 3 seconds
Wh and varh
display by turns.
Setting No.
It displays by
clear completion.
New setting Current setting
Setting factor
Wh and varh
display by
turns.