◆ 136 Power factor operation method
The operation method of power factor measurement can be selected from
0 (instantaneous measurement) and 1 (averaging operator in a demand
time interval).
In case it is set as "1 (averaging operator in a demand time interval)",
power factor measurement is calculated from the operation method of a
power demand time interval and a demand active power meter.
Selection by + and - , set value is updated by SET .
Default setting:0 (Instantaneous measurement )
(4) 141H to 14A Harmonic detection setting
Set the high-alarm value of each harmonic (current, voltage) measurement factor, factor,
5th conversion detection characteristics, and average time interval is performed.
◆ 141H Current distortion factor upper limit,
145H Voltage distortion factor upper limit.
Set the high-alarm value of distortion factor (current, voltage).
Setting range. Current:5 to 100% (1% step)
Voltage:1.0 to 20.0% (0.1% step)
Selection by + and - , set value is updated by SET .
Default setting:OFF [Non use] (Current, Voltage)
◆ 142H Current 5th conversion content upper limit,
146H Voltage 5th conversion content upper limit.
Set the high-alarm value of 5th conversion content
(current, voltage).
Setting range. Current:5 to 100% (1% step)
Voltage:1.0 to 20.0% (0.1% step)
Selection by + and - , set value is updated by SET .
Default setting:OFF [Non use] (Current, Voltage)
◆ 143 Current nth content factor,
147 Voltage nth content factor.
Set the factor (order) of nth content (current, voltage).
An order can be selected from n= 3, 4, 5, 7, 9, 11, 13, 15.
Selection by + and - , set value is updated by SET .
Default setting:5th (Current, Voltage)
◆ 144H Current nth content upper limit,
148H Voltage nth content upper limit.
Set the high-alarm value of nth content (current, voltage).
Setting range. Current:5 to 100% (1% step)
Voltage:1.0 to 20.0% (0.1% step)
Selection by + and - , set value is updated by SET .
Default setting:OFF [Non use] (Current, Voltage)
141H
Current distortion
factor
upper limit
RESET/
SHIFT
RESET/
SHIFT
142H
Current 5th
conversion content
upper limit
RESET/
SHIFT
RESET/
SHIFT
RESET/
SHIFT
143
Current nth
content factor
RESET/
SHIFT
144H
Current nth
content
upper limit
145H
Voltage distortion
factor
upper limit
RESET/
SHIFT
146H
Voltage 5th
conversion content
upper limit
147
Voltage nth
content factor
148H
Voltage nth
content
upper limit
RESET/
SHIFT
149
5th conversion
detection
characteristics
RESET/
SHIFT
14A
Average time
interval
RESET/
SHIFT
0:Instantaneous
measurement
1:
Averaging operator
in a demand time
interval
+
-
-
+
New setting
Current setting
Setting No.
Power factor operation method
Current distortion factor upper limit
Setting factor
Current setting
Setting No.
New setting
Voltage nth content factor
Setting factor
Current setting
Setting No.
New setting