9
3P130768-6L English
NOTE
•
If the wiring is in a place where people it can be easily
touched by people, install a leak interrupter to prevent
electric shock.
•
When using a ground-fault circuit interrupter, make sure
to select one useful also to protection against overcurrent
and short-circuit.
If you use a leak interrupter which is designed for protect-
ing again ground faults, be sure to combine it with a wir-
ing interrupter or an load switch that has a fuse.
•
The length of the transmission wiring and remote control-
ler wiring are as follows.
ELECTRICAL CHARACTERISTICS
MCA: Min. Circuit Amps (A)
MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW) FLA: Full Load Amps (A)
10 WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER
10. 1 OPENING AND SHUTTING THE CONTROL BOX
AND CONNECTING THE WIRING
CAUTION
Be sure to power off before opening the control box.
•
Remove the control box lid and wire as shown in the figure
below (Refer to Fig 17 and 18 for details).
CAUTION
•
See “Electrical Wiring Diagram label” on the backside of the
lid of the control box for electric wiring work.
•
Be sure to attach the sealing material or putty (locally pro-
cured) to hole of wiring to prevent the infiltration of water as
well as any insects and other small creatures from outside.
Otherwise a short-circuit may occur inside the control box.
•
When clamping the wires, be sure no pressure is applied to
the wire connections by using the included clamping material
to make appropriate clamps. Also, when wiring, make sure
the lid on the control box fits snugly by arranging the wires
neatly and attaching the control box lid firmly.
When attaching the control box lid, make sure no wires get
caught in the edges. Pass wiring through the wiring through
holes to prevent damage to them.
•
Make sure the remote controller wiring, the wiring between
the units, and other electrical wiring do not pass through the
same locations outside of the unit, separating them by at least
50 mm, otherwise electrical noise (external static) could
cause mistaken operation or breakage.
10. 2 CONNECTING POWER SUPPLY WIRING AND
GROUND WIRING
•
Pass the power supply wiring and the ground wiring through
the wiring through-hole into the control box and secure with
the included clamping material after connecting the wires to
terminal blocks.
(Refer to Fig. 17)
<Precautions when laying power supply wiring>
[PRECAUTIONS]
[1] A circuit breaker capable of shutting down power supply to
the entire system must be installed.
[2] A single switch can be used to supply power to units on the
same system.
However branch switches, branch overload circuit interrupter
must be selected carefully.
[3] Fit the power supply wiring of each unit with a switch and
fuse as shown in the drawing.
Length of outdoor-indoor transmission wiring
… max 1000 m (total wiring length 2000 m)
Length of remote controller wiring between indoor unit
and remote controller … max 500 m
Units
Power supply
Fan motor
Model
Hz
Volts
Voltage
range
MCA
MFA
kW
FLA
VKM50GBMV1,
VKM50GBV1
50
220-
240 V
Max.
264 V
Min.
198 V
3.25
15
0.21×2
1.3×2
VKM80GBMV1,
VKM80GBV1
3.25
15
0.21×2
1.3×2
VKM100GBMV1,
VKM100GBV1
3.25
15
0.21×2
1.3×2
Printed
circuit
board
Printed
circuit
board
Control box
Printed
circuit
board
Power wiring through-hole
Ground
terminal
Transmission wiring through-hole
Transmission
wiring
Power supply wiring
and Ground wiring
Terminal block (X1M) details
Short-circuit wire
Remove when
installing the humidistat
(Locally procured)
Grounding terminal
(M4 screw, spring
washer, cup washer)
Power supply wiring
Ground wiring
Wiring for the
humidistat
Resin Clamp parts
Clamp
(Accessory)
Fi
g
. 17
01_EN_3P130768-6L.fm 9 ページ 2013年3月21日 木曜日 午前11時48分
Содержание VKM100GBMV1
Страница 18: ...white page fm 1...
Страница 19: ...white page fm 2...
Страница 20: ...EM12A038 1303 3P130768 6L DE 00_CV_3P130768 6L fm 2...