background image

9

3P130768-6L   English

NOTE

If the wiring is in a place where people it can be easily 
touched by people, install a leak interrupter to prevent 
electric shock.

When using a ground-fault circuit interrupter, make sure 
to select one useful also to protection against overcurrent 
and short-circuit.
If you use a leak interrupter which is designed for protect-
ing again ground faults, be sure to combine it with a wir-
ing interrupter or an load switch that has a fuse.

The length of the transmission wiring and remote control-
ler wiring are as follows.

ELECTRICAL CHARACTERISTICS

MCA: Min. Circuit Amps (A) 

MFA: Max. Fuse Amps (A)

kW: Fan Motor Rated Output (kW)  FLA: Full Load Amps (A)

10 WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER

10. 1 OPENING AND SHUTTING THE CONTROL BOX 

AND CONNECTING THE WIRING

CAUTION

Be sure to power off before opening the control box.

Remove the control box lid and wire as shown in the figure 
below (Refer to Fig 17 and 18 for details).

CAUTION

See “Electrical Wiring Diagram label” on the backside of the
lid of the control box for electric wiring work.

Be sure to attach the sealing material or putty (locally pro-
cured) to hole of wiring to prevent the infiltration of water as 
well as any insects and other small creatures from outside. 
Otherwise a short-circuit may occur inside the control box.

When clamping the wires, be sure no pressure is applied to
the wire connections by using the included clamping material
to make appropriate clamps. Also, when wiring, make sure
the lid on the control box fits snugly by arranging the wires
neatly and attaching the control box lid firmly.
When attaching the control box lid, make sure no wires get
caught in the edges. Pass wiring through the wiring through
holes to prevent damage to them.

Make sure the remote controller wiring, the wiring between
the units, and other electrical wiring do not pass through the
same locations outside of the unit, separating them by at least
50 mm, otherwise electrical noise (external static) could
cause mistaken operation or breakage.

10. 2 CONNECTING POWER SUPPLY WIRING AND 

GROUND WIRING

Pass the power supply wiring and the ground wiring through 
the wiring through-hole into the control box and secure with 
the included clamping material after connecting the wires to 
terminal blocks. 

(Refer to Fig. 17)

<Precautions when laying power supply wiring>

[PRECAUTIONS]

[1] A circuit breaker capable of shutting down power supply to 

the entire system must be installed. 

[2] A single switch can be used to supply power to units on the 

same system.
However branch switches, branch overload circuit interrupter 
must be selected carefully.

[3] Fit the power supply wiring of each unit with a switch and 

fuse as shown in the drawing.

Length of outdoor-indoor transmission wiring 
… max 1000 m (total wiring length 2000 m)

Length of remote controller wiring between indoor unit 
and remote controller … max 500 m

Units

Power supply

Fan motor

Model

Hz

Volts

Voltage 

range

MCA

MFA

kW

FLA

VKM50GBMV1,
VKM50GBV1

50

220-

240 V

Max. 

264 V

Min. 

198 V

3.25

15

0.21×2

1.3×2

VKM80GBMV1,
VKM80GBV1

3.25

15

0.21×2

1.3×2

VKM100GBMV1,
VKM100GBV1

3.25

15

0.21×2

1.3×2

Printed 
circuit 
board 

Printed 
circuit 
board 

Control box

Printed 
circuit 
board 

Power wiring through-hole

Ground 
terminal

Transmission wiring through-hole

Transmission 
wiring

Power supply wiring 
and Ground wiring

Terminal block (X1M) details

Short-circuit wire
Remove when 
installing the humidistat
(Locally procured)

Grounding terminal
(M4 screw, spring 
washer, cup washer)

Power supply wiring
Ground wiring

Wiring for the 
humidistat

Resin Clamp parts

Clamp
(Accessory)

Fi

g

. 17

01_EN_3P130768-6L.fm  9 ページ  2013年3月21日 木曜日 午前11時48分

Содержание VKM100GBMV1

Страница 1: ...puchons de formes arrondies des grilles d aspiration vacuation d air avant l installation de cette unit Ventilaci n con recuperaci n de calor Por favor lea cuidadosamente el manual de instalacion e in...

Страница 2: ...icable for a certain product or domain Be sure to use only the specified parts and accessories for installation work Failure to use the specified parts may result in the Heat Reclaim Ventilator unit f...

Страница 3: ...ntil installation work is done 1 Decide upon a line of transport 2 Leave the unit inside its packaging while moving until reach ing the installation site Where unpacking is unavoidable use a sling of...

Страница 4: ...be sufficient enough to eliminate the electric noise The bellows may not be able to be used in some districts so exercise caution Contact your local government office or fire department for details Wh...

Страница 5: ...aring the weight of the unit Refer to Fig 3 5 THE METHOD OF INSTALLATION CAUTION Hold underside of the unit or hanger bracket without putting force on other parts when unpacking or moving the unit As...

Страница 6: ...greater than or equal to the diameter of the connecting pipe pipe size PT3 4B When piping passes indoors always insulate it all the way to the base of the drain socket In areas where freezing may occu...

Страница 7: ...ing that passes indoors After checking that the water supply piping connections do no leak insulate them using the included insulation as shown in Fig 10 Tighten both edges with clamping material Refe...

Страница 8: ...e connections Refer to Fig 14 CAUTION When brazing a pipe while feeding nitrogen inside the pipe make sure to set the nitrogen pressure to 0 02 MPa 0 2 kg cm 2 or less using the pressure reducing valv...

Страница 9: ...g and insects tends to swarm around the light minute insects may intrude indoors through the air supply opening and air filter In such cases the use of a high performance filter sold sep arately is re...

Страница 10: ...wiring through holes to prevent damage to them Make sure the remote controller wiring the wiring between the units and other electrical wiring do not pass through the same locations outside of the uni...

Страница 11: ...iring their respective terminal blocks 10 4 WIRING FOR THE HUMIDITY REGULATOR LOCALLY PROCURED VKM GBMV1 SERIES ONLY Pass into the control box together with the power wire through the power wiring thr...

Страница 12: ...Fuse Switch Power supply 220 240V 50 Hz F1 F2 F1 F2 R S P1 P2 F1 F2 T1 T2 Transmission wiring Outdoor unit IN D OUT D Control box Standard indoor unit A Standard indoor unit B Earth Earth Earth Remote...

Страница 13: ...ONTROL FORCED OFF AND ON OFF OPERATION Wire specifications and how to perform wiring Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller The equipment in...

Страница 14: ...AL button for more than four seconds with the unit in the normal mode to enter the local setting mode 2 Use the TEMPERATURE ADJUSTMENT button to select the desired MODE NO The code display will blink...

Страница 15: ...n 17 27 0 Approx 2500 hours Approx 1250 hours No counting Nighttime free cooling operation ON OFF and starting time 1 OFF ON 2hours later ON 4hours later ON 6hours later ON 8hours later Initial settin...

Страница 16: ...ting Heating humidification 21 C Cooling suction temperature at refrigerant heat exchanger 26 C Configurable range of set temperature Heating humidification 14 to 26 C Cooling 18 to 33 C The correlati...

Страница 17: ...listening for that clicking sound let the unit run for 30 minutes to make sure that humidifying operation is normal CAUTION If carpentry work is not completed when a test run is fin ished tell the cu...

Страница 18: ...white page fm 1...

Страница 19: ...white page fm 2...

Страница 20: ...EM12A038 1303 3P130768 6L DE 00_CV_3P130768 6L fm 2...

Отзывы: