background image

1

3P130768-6L   English

With DX coil & Humidifier

VKM50GBMV1

VKM80GBMV1

VKM100GBMV1

With DX coil 

VKM50GBV1

VKM80GBV1

VKM100GBV1

Total Heat Exchanger

Heat Reclaim Ventilator -with DX Coil-

Installation

manual

CONTENTS

1 SAFETY PRECAUTIONS ...............................................1
2 BEFORE INSTALLATION ...............................................2
3 SELECTING INSTALLATION SITE .................................3
4 PREPARATIONS BEFORE INSTALLATION ...................4
5 THE METHOD OF INSTALLATION ................................4
6 DRAIN PIPING AND WATER SUPPLY WORK...............5
7 REFRIGERANT PIPING WORK .....................................6
8 DUCT CONNECTION.....................................................8
9 ELECTRIC WIRING WORK............................................8

10 WIRING EXAMPLE AND HOW TO SET THE REMOTE 

CONTROLLER ...............................................................9

11 FIELD SETTING AND TEST RUN................................13

The original instructions are written in English. All other lan-
guages are translations of the original instructions.

1

SAFETY PRECAUTIONS

Be sure to follow this “SAFETY PRECAUTIONS”. This product comes 
under the term “appliances not accessible to the general public”.
This manual classifies the precautions into WARNINGS and CAU-
TIONS. Be sure to follow all the precautions below: They are all 
important for ensuring safety.

WARNING

..............Indicates a potentially hazardous situ-

ation which, if not avoided, could result 
in death or serious injury.

CAUTION

...............Indicates a potentially hazardous situa-

tion which, if not avoided, may result in 
minor or moderate injury. It may also be 
used to alert against unsafe practices.

After the installation is completed, test the Heat Reclaim Ventila-
tor unit and check if the Heat Reclaim Ventilator unit operates 
properly. Give the user adequate instructions concerning the use 
and cleaning of the Heat Reclaim Ventilator unit according to the 
Operation Manual. Ask the user to keep this manual and the 
Operation Manual together in a handy place for future reference.

WARNING

Ask your local dealer or qualified personnel to carry out 
installation work. Improper installation may result in water 
leakage, electric shocks or a fire.

Installation should be done following the installation manual and 
no changes should be made to the unit.
Improper installation may result in water leakage, electric shocks 
or a fire. Injuries may result if the Heat Reclaim Ventilator unit falls.

Install the Heat Reclaim Ventilator unit on a foundation that can 
withstand its mass. 
Insufficient strength may result in the Heat Reclaim Ventilator 
unit falling down and causing injury. In addition, it may lead to 
vibration of indoor units and cause unpleasant chattering noise.

Do not allow exhaust air to enter the outside air intake vent. 
This may cause the air of the room to become contaminated, 
harming the health.

Locate the outside air intake vent so that it does not take in 
exhaust air which contains combustion air, etc.
Incorrect installation may cause a loss of oxygen in the room, 
leading to serious accidents.

Make certain that all electrical work is carried out by qualified 
personnel according to the applicable legislation (note 1) and 
this installation manual, using a separate circuit.
In addition, even if the wiring is short, make sure to use a wir-
ing that has sufficient length and never connect additional 
wiring to make the length sufficient. Insufficient capacity of 

the power supply circuit or improper electrical construction 
may lead to electric shocks or a fire.
(note 1)

applicable legislation means “All international, 
national and local directives, laws, regulations and/
or codes which are relevant and applicable for a 
certain product or domain”.

Be sure to use only the specified parts and accessories for 
installation work. Failure to use the specified parts may result 
in the Heat Reclaim Ventilator unit falling down, water leak-
age, electric shocks, a fire, etc.

Carry out the specified installation work in consideration of strong 
winds, typhoons, or earthquakes. Improper installation may result 
in an accident such as Heat Reclaim Ventilator unit falling.

Make sure that all wiring is secure, using the specified wiring and ensur-
ing that external forces do not act on the terminal connections or wiring.
Incomplete connection or fixing may cause an overheat or a fire.

When wiring remote controller wiring and transmission wir-
ing, and wiring the power supply, form the wiring orderly so 
that the control box lid can be securely fastened. If the control 
box lid is not in place, overheat of the terminals, electric 
shocks or a fire may be caused.

Consult your local dealer regarding what to do in case of 
refrigerant leakage.
When the Heat Reclaim Ventilator unit is installed in a small 
room, it is necessary to take proper measures so that the 
amount of any leaked refrigerant does not exceed the con-
centration limit in the event of a leakage. Otherwise, this may 
lead to an accident due to oxygen deficiency.

If refrigerant gas leaks during installation work, ventilate the 
area immediately. Toxic gas may be produced if refrigerant 
gas comes into contact with a fire.

After completing the installation work, check to make sure that 
there is no leakage of refrigerant gas. Toxic gas may be pro-
duced if refrigerant gas leaks into the room and comes into con-
tact with a source of a fire, such as a fan heater, stove or cooker.

Disconnect the power supply before touching the electric compo-
nents. If you touch the live part, you may get an electric shocks.

Never directly touch any accidental leaking refrigerant. This 
could result in severe wounds caused by frostbite.

Earth the Heat Reclaim Ventilator unit. 
Do not connect the earth wiring to gas or water piping, lightning 
conductor or telephone earth wiring. Incomplete earthing may 
cause electric shocks or a fire. A high surge current from light-
ning or other sources may cause damage to the air conditioner.

• Be sure to install an earth leakage circuit breaker.

Failure to do so may cause electric shocks and a fire.

CAUTION

Install drain piping according to this installation manual to 
ensure good drainage, and insulate the piping to prevent 
condensation. Improper drain piping may cause water leak-
age, make the furniture get wet.

Install the Heat Reclaim Ventilator unit, power supply wiring, 
remote controller wiring and transmission wiring at least 1 
meter away from televisions or radios to prevent image inter-
ference or noise. (Depending on the radio waves, a distance 
of 1 meter may not be sufficient to eliminate the noise.)

Install the two outdoor ducts with down slope to prevent rain-
water from entering the unit. If this is not done completely, 
water may enter the building, may damage furniture, and 
cause electric shocks and fire.

Insulate the two outdoor ducts and the supply air duct to pre-
vent condensation. If this is not done completely, water may 
enter the building, may damage furniture, etc.

Insulate the duct and the wall electrically when a metal duct 
is to be penetrated through the metal lattice and wire lattice 
or metal lining of a wooden structure wall. Improper duct 
work may cause electric shocks or fire.

01_EN_3P130768-6L.fm  1 ページ  2013年3月21日 木曜日 午前11時48分

Содержание VKM100GBMV1

Страница 1: ...puchons de formes arrondies des grilles d aspiration vacuation d air avant l installation de cette unit Ventilaci n con recuperaci n de calor Por favor lea cuidadosamente el manual de instalacion e in...

Страница 2: ...icable for a certain product or domain Be sure to use only the specified parts and accessories for installation work Failure to use the specified parts may result in the Heat Reclaim Ventilator unit f...

Страница 3: ...ntil installation work is done 1 Decide upon a line of transport 2 Leave the unit inside its packaging while moving until reach ing the installation site Where unpacking is unavoidable use a sling of...

Страница 4: ...be sufficient enough to eliminate the electric noise The bellows may not be able to be used in some districts so exercise caution Contact your local government office or fire department for details Wh...

Страница 5: ...aring the weight of the unit Refer to Fig 3 5 THE METHOD OF INSTALLATION CAUTION Hold underside of the unit or hanger bracket without putting force on other parts when unpacking or moving the unit As...

Страница 6: ...greater than or equal to the diameter of the connecting pipe pipe size PT3 4B When piping passes indoors always insulate it all the way to the base of the drain socket In areas where freezing may occu...

Страница 7: ...ing that passes indoors After checking that the water supply piping connections do no leak insulate them using the included insulation as shown in Fig 10 Tighten both edges with clamping material Refe...

Страница 8: ...e connections Refer to Fig 14 CAUTION When brazing a pipe while feeding nitrogen inside the pipe make sure to set the nitrogen pressure to 0 02 MPa 0 2 kg cm 2 or less using the pressure reducing valv...

Страница 9: ...g and insects tends to swarm around the light minute insects may intrude indoors through the air supply opening and air filter In such cases the use of a high performance filter sold sep arately is re...

Страница 10: ...wiring through holes to prevent damage to them Make sure the remote controller wiring the wiring between the units and other electrical wiring do not pass through the same locations outside of the uni...

Страница 11: ...iring their respective terminal blocks 10 4 WIRING FOR THE HUMIDITY REGULATOR LOCALLY PROCURED VKM GBMV1 SERIES ONLY Pass into the control box together with the power wire through the power wiring thr...

Страница 12: ...Fuse Switch Power supply 220 240V 50 Hz F1 F2 F1 F2 R S P1 P2 F1 F2 T1 T2 Transmission wiring Outdoor unit IN D OUT D Control box Standard indoor unit A Standard indoor unit B Earth Earth Earth Remote...

Страница 13: ...ONTROL FORCED OFF AND ON OFF OPERATION Wire specifications and how to perform wiring Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller The equipment in...

Страница 14: ...AL button for more than four seconds with the unit in the normal mode to enter the local setting mode 2 Use the TEMPERATURE ADJUSTMENT button to select the desired MODE NO The code display will blink...

Страница 15: ...n 17 27 0 Approx 2500 hours Approx 1250 hours No counting Nighttime free cooling operation ON OFF and starting time 1 OFF ON 2hours later ON 4hours later ON 6hours later ON 8hours later Initial settin...

Страница 16: ...ting Heating humidification 21 C Cooling suction temperature at refrigerant heat exchanger 26 C Configurable range of set temperature Heating humidification 14 to 26 C Cooling 18 to 33 C The correlati...

Страница 17: ...listening for that clicking sound let the unit run for 30 minutes to make sure that humidifying operation is normal CAUTION If carpentry work is not completed when a test run is fin ished tell the cu...

Страница 18: ...white page fm 1...

Страница 19: ...white page fm 2...

Страница 20: ...EM12A038 1303 3P130768 6L DE 00_CV_3P130768 6L fm 2...

Отзывы: