87
Intelligent PDU User Guide
Commad Line Interface
To display outlet load configuration
CyberPower >
oltloadcfg show
Example 2:
To set overload threshold of outlet #1 at 1800W
CyberPower >
oltloadcfg index 1 overload 1800
Example 3:
To set near overload threshold of outlet #2 at 1000W
CyberPower >
oltloadcfg index 2 nearover 1000
Example 4:
To set low load threshold of outlet #10 at 100W
CyberPower >
oltloadcfg index 10 lowload 100
schedule
Description: Show and configure the outlet schedule of device.
Option
Argument
Description
show
Show information of schedule.
guest
1
|
2
|
3
Set daisy chain index.
index
1 | 2 |…| schedule number
|
10
Select schedule index.
add
once | daily | weekly
add
– Add new schedule of outlet
once
– Add schedule as once frequency
daily
– Add schedule as daily frequency
weekly
– Add schedule as weekly frequency
After finish this command, input schedule
name and step by step.
The parameters of
action
on | off | reboot | delayon | delayoff |
delayreboot
The parameters of
month
1| 2|
…… |12
The Parameters of day of
week
Mon | Tue | Wed | Thu | Fri | Sat | Sun
The Parameters of
day
1| 2| 3|
…… |31
The Parameters of
hour
1| 2| 3|
…… |24
Содержание PDU31 Series
Страница 17: ...15 Web Interface Intelligent PDU User Guide For Switched Metered by Outlet Series only ...
Страница 30: ...28 Web Interface Intelligent PDU User Guide Configure E mail Recipient Page Add New E mail Recipient Page ...
Страница 32: ...30 Web Interface Intelligent PDU User Guide Configure Trap Receiver Page Add New Trap Receiver Page ...
Страница 39: ...37 Web Interface Intelligent PDU User Guide Configure SMS Receiver Page Add New SMS Receiver Page ...
Страница 61: ...59 Web Interface Intelligent PDU User Guide Administrator Page Viewer Page ...