Appendix C-PDU Daisy-Chain Function

How to switch between Host and Guest ATS PDUs on the Web interface?

Functionality supported by daisy-chained ATS PDUs will have the Host/ 
Guest # drop down menu displayed on the Web interface (as shown below).

Can I upgrade the firmware version of the Guest ATS PDUs through the 
Host PDU?

Yes, you can upgrade the firmware using the Upgrade and Configuration 
Utility, FTP (network connection required), or USB port. Once the Host 
completes the ATS PDU firmware upgrade, it will trigger its Guest ATS PDUs 
to upgrade the firmware automatically. It takes about 5 minutes for the Guest 
ATS PDUs to upgrade, regardless of the number of ATS PDUs in the series.

What will happen if an Ethernet cable is disconnected in the ATS PDUs 
daisy-chain?

For example, if four ATS PDUs are connected and the cable connecting Guest 
1 and 2 is disconnected, then Guest 2 and 3 will no longer be detected by 
the Host ATS PDU. An event showing that Guest 2 and 3 are removed will be 
recorded in the Host ATS PDU. Meanwhile, Guest 2 and 3 will create a new 
daisy-chain where Guest 2 becomes a Host and Guest 3 becomes Guest 1 to 
the new Host.

In the above example, if the disconnected Ethernet cable is re-connected, 
will the role of the ATS PDUs stay the same?

Yes, when the disconnected cable between Guest 1 and 2 is re-connected, 
Guest 2 and 3 will revert to their previous roles.

What happens if one ATS PDU in the daisy-chain is powered off?

For example, if four ATS PDUs are connected and Guest 1 is powered off, an 
event showing that Guest 1, 2 and 3 are removed will be recorded in the Host 
ATS PDU. Guest 2 and 3 will not create another daisy-chain.

Does the Host ATS PDU record the logs of the Guest ATS PDUs and itself?

Yes, the Host ATS PDU records the logs from all Guest ATS PDUs daisy-
chained to it.

Will the Logs of the Guest ATS PDUs recorded in the Host ATS PDU be 
cleared if the Guest ATS PDUs are removed from the Host ATS PDU?

No, the Logs of the Guest ATS PDUs will remain even after the Guest ATS 
PDUs are removed.

Can I upgrade the firmware version of the Guest PDUs through the Host PDU?

Yes, you can upgrade the firmware using the Upgrade and Configuration Utility, 

FTP (network connection required), or USB port. Once the Host completes the 

PDU firmware upgrade, it will trigger its Guest PDUs to upgrade the firmware 

automatically. It takes about 5 minutes for the Guest PDUs to upgrade, 

regardless of the number of PDUs in the series.

What will happen if an Ethernet cable is disconnected in the PDU daisy-chain? 

For example, if four PDUs are connected and the cable connecting Guest 1 and 2 

is disconnected, then Guest 2 and 3 will no longer be detected by the Host PDU. 

An event showing that Guest 2 and 3 are removed will be recorded in the Host 

PDU. Meanwhile, Guest 2 and 3 will create a new daisy-chain where Guest 2 

becomes a Host and Guest 3 becomes Guest 1 to the new Host.

In the above example, if the disconnected Ethernet cable is re-connected, will 

the role of the PDUs stay the same?

Yes, when the disconnected cable between Guest 1 and 2 is re-connected, 

Guest 2 and 3 will revert to their previous roles.

What happens if one PDU in the daisy-chain is powered off?

For example, if four PDUs are connected and Guest 1 is powered off, an event 

showing that Guest 1, 2 and 3 are removed will be recorded in the Host PDU. 

Guest 2 and 3 will not create another daisy-chain.

Does the Host PDU record the logs of the Guest PDUs and itself?

Yes, the Host PDU records the logs from all Guest PDUs daisy-chained to it.

Will the Logs of the Guest PDUs recorded in the Host PDU be cleared if the 

Guest PDUs are removed from the Host PDU?

No, the Logs of the Guest PDUs will remain even after the Guest PDUs are removed.

Does the Host PDU record the Status Records of the Guest PDUs and itself?

Yes, the Host PDU records the Status Records for all the PDUs in the 

daisy-chain.

Will the Status Records of the Guest PDUs logged in the Host PDU be cleared 

if the Guest PDUs are disconnected from the Host PDU?

Yes, once the Guest PDUs are removed, the Status Records logged in the Host 

PDU will be cleared. As long as the Host PDU does not connect to other PDUs, 

the Status Records of the disconnected PDU can be displayed when it is 

re-connected to the Host PDU. If the Host PDU connects to different PDUs, the 

Status Records of the removed PDU will be entirely cleared.

K01-E000006-01

Cyber Power Systems, Inc.

www.cyberpowersystems.com

Problem

The PDUs are 

connected but the 

daisy-chain function is 

not working.

I cannot set the 

EnergyWise 

configuration on a 

Guest PDU.
I cannot set the WoL 

for Guest PDUs.

Possible Cause

- The firmware version 

does not support 

daisy-chain.

- The PDUs have 

different firmware 

versions.

Only the Host PDU 

supports EnergyWise.

Only the Host PDU 

supports WoL.

Solution

Check the firmware 

version of each PDU 

and upgrade it to v1.07 

or above.

N/A

N/A

Troubleshooting

Host

Guest #1

Guest #2

Host

Guest #3

Guest #1

Are the Guest PDUs able to connect to the network when they are 

daisy-chained?

Yes, even when the PDUs are daisy-chained, the Guest PDUs are able to 

connect to the network directly. Note that a Guest PDU will require having its 

own Ethernet cable connected to the network. 

What will happen if a 5

th

 PDU is added to a daisy-chain?

The maximum number of PDUs that can be connected in one daisy-chain is 4. 

The daisy-chain functionality will not work until the fifth PDU is removed.

What is the maximum recommended length of the Ethernet cable to 

daisy-chain the PDUs?

50 ft (15 m)

Ethernet

Содержание PDU24001

Страница 1: ...Automatic Transfer Switch USER S MANUAL Copyright 2021 Cyber Power Systems Inc All rights reserved K01 0000929 01...

Страница 2: ......

Страница 3: ...For 2U Models 12 Rear Mounting 13 For 1U Models 13 For 2U Models 15 Replacing LCD Panel 17 Electrical Installation 17 Locking Power Cord For IEC Type ATS PDU 18 Input Power Cord 18 Output Power Cord 1...

Страница 4: ...PDU74002 PDU74004 PDU74005 PDU74006 PDU74301 PDU74003 PDU74007 PDU74302 Switched Series Monitored Series 1U 2U 1U 2U PDU44001 PDU44002 PDU44004 PDU44005 PDU44006 PDU44301 PDU44003 PDU44007 PDU44302 PD...

Страница 5: ...0A Pour la s rie PDU 30A veuillez utiliser un disjoncteur de 30A La connexion tout autre type de prise de courant peut provoquer un choc lectrique N utilisez pas de rallonges ni d adaptateurs avec ces...

Страница 6: ...y For 1U Models Product Contents ATS PDU Cable Ties Qty 18 NEMA Outlet Qty 30 IEC Outlet RJ45 DB9 Serial Port Connection Cable Mounting Bracket x 2 24 M4x8 Bracket Mounting Screws Includes eight spare...

Страница 7: ...cludes two spares for each Cord Retention Tray X 2 12 M3x6 Cord Retention Tray Mounting Screws Includes two spares for each User s Manual and Software Download Card Users Manual PowerPanel Management...

Страница 8: ...10 2 1 Critical Warning Normal USB Serial Enter Select SOURCE A SOURCE A 15A SOURCE B 15A SOURCE B 1 2 3 4 5 6 7 8 9 10 11 12 Critical Warning Normal Link Tx Rx In ENV USB Out Serial Enter Select A B...

Страница 9: ...y Outlet Switched Monitor Series A B C D E F G H I J K L M N O P Source Status Indicator Indicates the status of Source A and B Source Selected Indicator Indicates Source A or B is in use Output Indic...

Страница 10: ...Metered by Outlet Switched Monitor Series Source Status Indicator Indicates the status of Source A and B Source Selected Indicator Indicates Source A or B is in use Output Indicator Indicates the outp...

Страница 11: ...PDU24007 Input Nominal Voltage 100 120V 200 240V 100 120V 200 240V Frequency 50 60Hz Derated Input Current 24A Plug Type 2 NEMA L5 30P 2 NEMA L6 30P 2 NEMA L5 30P 2 NEMA L6 30P Power Cord Type SR 10...

Страница 12: ...ing Normal USB Serial Enter Select D E H A B A B C L I K M N O P Q BANK 1 20A BANK 2 20A 1 2 3 4 13 12 11 10 14 15 16 17 8 7 6 5 9 18 Source Status Indicator Indicates the status of Source A and B Sou...

Страница 13: ...er sources are compatible with this ATS PDU Simulated sine wave AC power sources are NOT compatible CyberPower Sinewave UPS CyberPower Online UPS Utility Power Utility Power Utility Power CyberPower O...

Страница 14: ...d ATS PDU are aligned Attach the Cord Retention Tray to the ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws Tighten the Cord Retention Tray with the screw on it Step 3 ATS PDU Mounting...

Страница 15: ...16 to attach the Mounting Brackets 2 to the ATS PDU Step 2 Cord Retention Tray Installation optional Adjust the length of the Cord Retention Trays till the screw hole on the Trays and ATS PDU are ali...

Страница 16: ...rew sets provided by the rack to secure the ATS PDU Step 4 Cable Ties Optional Use the provided Cable Ties to fasten each cord to the Cord Retention Tray Rear Mounting For 1U Models Step 1 Mounting Br...

Страница 17: ...t the length of the Cord Retention Tray till the screw hole on the Tray and ATS PDU are aligned Attach the Cord Retention Tray to the ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws Ti...

Страница 18: ...Step 1 Mounting Bracket Installation Use the provided Mounting Bracket Screws 16 to attach the Mounting Brackets 2 to the ATS PDU If you plan on attaching the Cord Retention Tray to the ATS PDU use th...

Страница 19: ...o the ATS PDU with the 8 supplied Cord Retention Tray Mounting Screws Tighten the Cord Retention Trays with the screw on it Step 3 ATS PDU Mounting Use the provided Washers 4 and Screws 4 to secure th...

Страница 20: ...st also be connected to an appropriate branch circuit main with fuse or circuit breaker protection Connection to any other type of receptacle may result in an electrocution hazard Step 2 Plug the ATS...

Страница 21: ...d Stand and fasten it as shown below Step 2 Align and insert the Cable Tie from the bottom side of the Fixed Stand and fasten it as shown below Output Power Cord Step 1 Align and insert the Cable Tie...

Страница 22: ...ation instructions see Appendix B Option 2 DHCP Server 1 Ask your administrator if there is DHCP server on the LAN 2 Make sure the DHCP is Enabled 3 Make sure the network connection is ready and power...

Страница 23: ...SNMP supported management software Default read write community is public private for SNMPv1 SNMPv3 provides a higher security level than SNMPv1 by encrypting the transmitted packet Configure the sett...

Страница 24: ...ttended Automatic Shutdown PowerPanel Business Remote software automatically initiates a graceful shutdown on the connected computer s operating system PowerPanel must be installed on every computer o...

Страница 25: ...t turn the ATS PDU off when performing the firmware upgrade ATS PDU outlets will remain powered on while the firmware update takes place Only the ATS PDU LCD screen will reboot 3 The ATS PDU LCD scree...

Страница 26: ...the Upgrade and Configuration Utility from www cyberpower com 2 Open Upgrade and Configuration Utility from Start All Programs CyberPower Upgrade and Configuration Utility 3 Wait for search to finish...

Страница 27: ...data file to be updated Shown in Figure 4 Figure 4 8 Click OK in the Upgrade Firmware confirmation window Shown in Figure 5 9 The upgrade progress bar will show in Last Action column Shown in Figure...

Страница 28: ...n and Yes to start the upgrade process 6 The ATS PDU will reboot after the process is completed Note You can check to see if the firmware upgrade is successful by checking the Firmware version on the...

Страница 29: ...psmpdumafw_XXX bin and cpsmpdumadata_XXX bin In order to upgrade the firmware version both files need to be uploaded Only one firmware file can be uploaded at a time it is recommended to upload the fi...

Страница 30: ...appareil numerique de la class A respecte toutes les exigencies du Reglement sur le materiel brouilleur du Canada European Union This is a class A product In a domestic environment this product may c...

Страница 31: ...for Shipping We pay when we send items to you you pay when you send items to us What Are Some Things This Warranty Does Not Cover 1 This Warranty does not cover any software that is damaged or needs...

Страница 32: ...6 Account Settings 7 Configure System to Default 8 Logout Utility Configuration 1 Preferred Source A 2 Sensitivity High 3 Voltage Range Medium 4 Frequency Deviation 1 Hz 5 Nominal Voltage 230 V 6 Wide...

Страница 33: ...ddresses on CyberPower ATS PDUs Installation Step 1 Download the Power Device Network Utility software from www cyberpower com Step 2 Select Next in the software wizard Shown in Figure 1 Step 3 Choose...

Страница 34: ...h a specific IP address subnet mask and gateway address This allows the device s to function properly on the network and interface with CyberPower Management Console Step 1 Select the appropriate ATS...

Страница 35: ...ord of the ATS PDU at the Authentication menu shown in Figure 9 Note The default username is cyber and the default password is cyber Figure 9 Authentication screen Advanced Settings Timeout Settings T...

Страница 36: ...hain In ENV port on the Guest 1 ATS PDU to connect the ATS PDUs as shown below How to connect the PDUs together Use one Ethernet cable and connect one end of it to the daisy chain Out port on the Host...

Страница 37: ...he Guest PDUs through the Host PDU Yes you can upgrade the firmware using the Upgrade and Configuration Utilit FTP network connection required or USB port Once the Host completes th PDU firmware upgra...

Страница 38: ...d the Guest ATS PDUs are able to connect to the network directly Note that a Guest ATS PDU will require having its own Ethernet cable connected to the network What will happen if a 5th ATS PDU is adde...

Страница 39: ......

Страница 40: ...Cyber Power Systems Inc www cyberpower com Copyright 2021 Cyber Power Systems Inc All rights reserved K01 0000929 01...

Отзывы: