19
Step 1 – Network Connection
Using an Ethernet cable, attach one end to the Ethernet port on the
front of the ATS PDU, and the other end to a network port.
Step 2 – Establish the ATS PDU IP address
Assigning an IP address to the CyberPower ATS PDU requires the
user to have an available IP address that is valid on the respective
network. If an available IP address is unknown, contact the network
administrator to obtain one.
DHCP is enabled by factory default. If the ATS PDU does not receive an IP
address from the network's DHCP server, it will default to 192.168.20.177.
There are multiple methods for setting up the IP address of the ATS PDU
Please follow the instructions below for the method that is appropriate for your
application.
Please make sure the ATS PDU is powered on during this process.
Option 1: Power Device Network Utility (recommended)
1. Download and install the Power Device Network Utility software from
www.cyberpower.com.
2. Open the Power Device Network Utility and select the ATS PDU device from
the list and select Tools > Device Setup from the menu.
3. Configure the IP Address, Subnet Mask, and Gateway Address to match
your network settings.
4. Enter the user name and password of the ATS PDU device at the Authentication
menu.
Note:
The default username is “
cyber
” and the default password is “
cyber
”. For
further information and installation instructions, see Appendix B.
Option 2: DHCP Server
1. Ask your administrator if there is DHCP server on the LAN.
2. Make sure the DHCP is Enabled.
3. Make sure the network connection is ready and power on the ATS PDU.
4. The ATS PDU will obtain an IP address from the DHCP server automatically.
Option 3: Address Resolution Protocol (ARP) Command
1. Obtain the MAC address from the sticker on the ATS PDU.
2. Open a command prompt as an administrator and type the following:
“arp -s [available IP address] [MAC address of ATS PDU]”.
Example:
arp -s 192.168.20.240
00-0C-15-00-00-01
IP Address
MAC Address
3. Use the Ping command to assign a size of 123 bytes to the IP.
* Type in “
ping 192.168.20.240 -l 123
” then press
Enter
.
* If the replies are received, your computer can communicate with the IP
address.
Option 4: Hyper Terminal or Terminal Emulator
1. Use the included RJ45/DB9 serial port connection cable, attach one end to
the serial port on the front of the ATS PDU, and the other end to the PC/server.
2. Open the Hyper Terminal software on your PC and select a name and icon for
the connection.
3. Setup the COM port settings using the values indicated in Appendix A.
4. Press
Enter
to enter the Authentication menu.
5. Enter the user name and password of the ATS PDU device at the Authentication
menu.
6. Press
4
and
Enter
to access Network Settings to view the IP address.
Note:
The default username is “
cyber
” and the default password is “
cyber
”.
For further information and configuration via Hyper Terminal, see
Appendix A-Hyper Terminal.
Network Installation
Installation Guide