CyberPower PDU24001 Скачать руководство пользователя страница 23

20

Operation

Remote Management

The remote management function provides for monitoring of the ATS PDU 
operational information, controlling outlets and utilizing SNMP functionality.

Web

Remote management can be performed via web interface. To access the web 
interface, please follow the instructions below:
1.  Enter the IP address of the ATS PDU into a web browser.
2. Enter the user name and password of the ATS PDU device at the 

authentication screen. 

Note:

 The default username is “

cyber

” and the default password is “

cyber

”.

Telnet and SSH

The CyberPower ATS PDU provides Telnet and Secure Shell (SSH) as Remote 
Management methods. Telnet uses user name and password as basic security 
while SSH has a higher security level with encryption of the transmitted 
packets including user name, password, and data. Configure the Setting of 
Telnet and SSH on the Web Interface. The default user name and password is 

cyber

/

cyber

.

SNMP

The CyberPower ATS PDU supports SNMPv1 and SNMPv3 protocols. 
Download the CyberPower MIB file from www.cyberpower.com and add it 
to a SNMP-supported management software. Default read/write community 
is public/private for SNMPv1. SNMPv3 provides a higher security level than 
SNMPv1 by encrypting the transmitted packet. Configure the settings of the 
SNMPv1/SNMPv3 on Web Interface. 

Local Management

LCD Operation

The LCD screen provides instant information, such as source condition, voltage 
and current, for the ATS PDU. In addition, users can use the interface to configure 
each ATS PDU  parameters and control each outlet on the switched ATS PDU.
A.  Scroll Mode: The ATS PDU information will display in following order 

automatically when “Scroll Mode On” is configured.

Source A Information
Source B Information
Device Load
Environment Status (Displays when the ENVIROSENSOR is connected)
Alert Number

B. Main Menu Map

Alert

Current

Log

Meter

Source

Device

Outlet

Control

Outlet

All

Immediate On

Delay On

Bank 1/2

Immediate Off

Delay Off

Outlet 1-N

Reboot

Delay Reboot

Sensor

Setting

Source

Preferred Source

A/B/None

Voltage

Nominal Voltage

Voltage Range

Sensitivity

Frequency Deviation

1/2/3 Hz

LCD

Color

Brightness

Direction
Scren off

Reset

Account  

(User Name and 

Password)

Except TCP

To Defautl

Reboot

About

Model Name

Serial Number

Network

Daisy Chain

Hardware Version

Filmware Version

Содержание PDU24001

Страница 1: ...Automatic Transfer Switch USER S MANUAL Copyright 2021 Cyber Power Systems Inc All rights reserved K01 0000929 01...

Страница 2: ......

Страница 3: ...For 2U Models 12 Rear Mounting 13 For 1U Models 13 For 2U Models 15 Replacing LCD Panel 17 Electrical Installation 17 Locking Power Cord For IEC Type ATS PDU 18 Input Power Cord 18 Output Power Cord 1...

Страница 4: ...PDU74002 PDU74004 PDU74005 PDU74006 PDU74301 PDU74003 PDU74007 PDU74302 Switched Series Monitored Series 1U 2U 1U 2U PDU44001 PDU44002 PDU44004 PDU44005 PDU44006 PDU44301 PDU44003 PDU44007 PDU44302 PD...

Страница 5: ...0A Pour la s rie PDU 30A veuillez utiliser un disjoncteur de 30A La connexion tout autre type de prise de courant peut provoquer un choc lectrique N utilisez pas de rallonges ni d adaptateurs avec ces...

Страница 6: ...y For 1U Models Product Contents ATS PDU Cable Ties Qty 18 NEMA Outlet Qty 30 IEC Outlet RJ45 DB9 Serial Port Connection Cable Mounting Bracket x 2 24 M4x8 Bracket Mounting Screws Includes eight spare...

Страница 7: ...cludes two spares for each Cord Retention Tray X 2 12 M3x6 Cord Retention Tray Mounting Screws Includes two spares for each User s Manual and Software Download Card Users Manual PowerPanel Management...

Страница 8: ...10 2 1 Critical Warning Normal USB Serial Enter Select SOURCE A SOURCE A 15A SOURCE B 15A SOURCE B 1 2 3 4 5 6 7 8 9 10 11 12 Critical Warning Normal Link Tx Rx In ENV USB Out Serial Enter Select A B...

Страница 9: ...y Outlet Switched Monitor Series A B C D E F G H I J K L M N O P Source Status Indicator Indicates the status of Source A and B Source Selected Indicator Indicates Source A or B is in use Output Indic...

Страница 10: ...Metered by Outlet Switched Monitor Series Source Status Indicator Indicates the status of Source A and B Source Selected Indicator Indicates Source A or B is in use Output Indicator Indicates the outp...

Страница 11: ...PDU24007 Input Nominal Voltage 100 120V 200 240V 100 120V 200 240V Frequency 50 60Hz Derated Input Current 24A Plug Type 2 NEMA L5 30P 2 NEMA L6 30P 2 NEMA L5 30P 2 NEMA L6 30P Power Cord Type SR 10...

Страница 12: ...ing Normal USB Serial Enter Select D E H A B A B C L I K M N O P Q BANK 1 20A BANK 2 20A 1 2 3 4 13 12 11 10 14 15 16 17 8 7 6 5 9 18 Source Status Indicator Indicates the status of Source A and B Sou...

Страница 13: ...er sources are compatible with this ATS PDU Simulated sine wave AC power sources are NOT compatible CyberPower Sinewave UPS CyberPower Online UPS Utility Power Utility Power Utility Power CyberPower O...

Страница 14: ...d ATS PDU are aligned Attach the Cord Retention Tray to the ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws Tighten the Cord Retention Tray with the screw on it Step 3 ATS PDU Mounting...

Страница 15: ...16 to attach the Mounting Brackets 2 to the ATS PDU Step 2 Cord Retention Tray Installation optional Adjust the length of the Cord Retention Trays till the screw hole on the Trays and ATS PDU are ali...

Страница 16: ...rew sets provided by the rack to secure the ATS PDU Step 4 Cable Ties Optional Use the provided Cable Ties to fasten each cord to the Cord Retention Tray Rear Mounting For 1U Models Step 1 Mounting Br...

Страница 17: ...t the length of the Cord Retention Tray till the screw hole on the Tray and ATS PDU are aligned Attach the Cord Retention Tray to the ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws Ti...

Страница 18: ...Step 1 Mounting Bracket Installation Use the provided Mounting Bracket Screws 16 to attach the Mounting Brackets 2 to the ATS PDU If you plan on attaching the Cord Retention Tray to the ATS PDU use th...

Страница 19: ...o the ATS PDU with the 8 supplied Cord Retention Tray Mounting Screws Tighten the Cord Retention Trays with the screw on it Step 3 ATS PDU Mounting Use the provided Washers 4 and Screws 4 to secure th...

Страница 20: ...st also be connected to an appropriate branch circuit main with fuse or circuit breaker protection Connection to any other type of receptacle may result in an electrocution hazard Step 2 Plug the ATS...

Страница 21: ...d Stand and fasten it as shown below Step 2 Align and insert the Cable Tie from the bottom side of the Fixed Stand and fasten it as shown below Output Power Cord Step 1 Align and insert the Cable Tie...

Страница 22: ...ation instructions see Appendix B Option 2 DHCP Server 1 Ask your administrator if there is DHCP server on the LAN 2 Make sure the DHCP is Enabled 3 Make sure the network connection is ready and power...

Страница 23: ...SNMP supported management software Default read write community is public private for SNMPv1 SNMPv3 provides a higher security level than SNMPv1 by encrypting the transmitted packet Configure the sett...

Страница 24: ...ttended Automatic Shutdown PowerPanel Business Remote software automatically initiates a graceful shutdown on the connected computer s operating system PowerPanel must be installed on every computer o...

Страница 25: ...t turn the ATS PDU off when performing the firmware upgrade ATS PDU outlets will remain powered on while the firmware update takes place Only the ATS PDU LCD screen will reboot 3 The ATS PDU LCD scree...

Страница 26: ...the Upgrade and Configuration Utility from www cyberpower com 2 Open Upgrade and Configuration Utility from Start All Programs CyberPower Upgrade and Configuration Utility 3 Wait for search to finish...

Страница 27: ...data file to be updated Shown in Figure 4 Figure 4 8 Click OK in the Upgrade Firmware confirmation window Shown in Figure 5 9 The upgrade progress bar will show in Last Action column Shown in Figure...

Страница 28: ...n and Yes to start the upgrade process 6 The ATS PDU will reboot after the process is completed Note You can check to see if the firmware upgrade is successful by checking the Firmware version on the...

Страница 29: ...psmpdumafw_XXX bin and cpsmpdumadata_XXX bin In order to upgrade the firmware version both files need to be uploaded Only one firmware file can be uploaded at a time it is recommended to upload the fi...

Страница 30: ...appareil numerique de la class A respecte toutes les exigencies du Reglement sur le materiel brouilleur du Canada European Union This is a class A product In a domestic environment this product may c...

Страница 31: ...for Shipping We pay when we send items to you you pay when you send items to us What Are Some Things This Warranty Does Not Cover 1 This Warranty does not cover any software that is damaged or needs...

Страница 32: ...6 Account Settings 7 Configure System to Default 8 Logout Utility Configuration 1 Preferred Source A 2 Sensitivity High 3 Voltage Range Medium 4 Frequency Deviation 1 Hz 5 Nominal Voltage 230 V 6 Wide...

Страница 33: ...ddresses on CyberPower ATS PDUs Installation Step 1 Download the Power Device Network Utility software from www cyberpower com Step 2 Select Next in the software wizard Shown in Figure 1 Step 3 Choose...

Страница 34: ...h a specific IP address subnet mask and gateway address This allows the device s to function properly on the network and interface with CyberPower Management Console Step 1 Select the appropriate ATS...

Страница 35: ...ord of the ATS PDU at the Authentication menu shown in Figure 9 Note The default username is cyber and the default password is cyber Figure 9 Authentication screen Advanced Settings Timeout Settings T...

Страница 36: ...hain In ENV port on the Guest 1 ATS PDU to connect the ATS PDUs as shown below How to connect the PDUs together Use one Ethernet cable and connect one end of it to the daisy chain Out port on the Host...

Страница 37: ...he Guest PDUs through the Host PDU Yes you can upgrade the firmware using the Upgrade and Configuration Utilit FTP network connection required or USB port Once the Host completes th PDU firmware upgra...

Страница 38: ...d the Guest ATS PDUs are able to connect to the network directly Note that a Guest ATS PDU will require having its own Ethernet cable connected to the network What will happen if a 5th ATS PDU is adde...

Страница 39: ......

Страница 40: ...Cyber Power Systems Inc www cyberpower com Copyright 2021 Cyber Power Systems Inc All rights reserved K01 0000929 01...

Отзывы: