7
Metered Series
IEC Type
Technical Specifications
Model Name
PDU84005
PDU74005
PDU44005
PDU34005
PDU84301
PDU74301
PDU44301
PDU34301
PDU24005
PDU24301
Input
Nominal Voltage
200-240V
Frequency
50/60Hz
Derated Input Current
16A
Plug TypePlug Type
(2) IEC-320 C20
(2) IEC 309 16A
(2) IEC-320 C20
(2) IEC 309 16A
Power Cord Type
Socket
Power Cord Length
10 ft/3.05 m
Circuit Breaker
Yes
No
Yes
No
Output
Nominal Voltage
200-240V
Derated Output Current
C13: 12A (UL)
10A (CE)
C19: 16A
C13: 10A (CE)
C19: 16A
C13: 12A (UL)
10A (CE)
C19: 16A
C13: 10A (CE)
C19: 16A
Outlet Type
(8) IEC C13
(2) IEC C19
Outlet Number
8+2
Management and Communications
Multifunction LCD Readout
Voltage, Frequency, Load, Current,
HW/FW Version, Network Information
Voltage, Frequency, Load, Current,
HW Version
Software
PowerPanel® Business
PowerPanel® Enterprise
No
Networking
Yes
No
Serial Port
RJ45
Sensor Capable
Optional
No
Physical
Dimension (H x W x D)
1.75" x 17.05" x 8.45"/ 44mm x 433mm x 215mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
13100 ft/4000 m
Temperature
32
o
F to 113
o
F/0
o
C to 45
o
C
Safety Approvals
Certifications
UL62368-1,
CE EN55032/24,
FCC Class A
CB,
CE EN55032/24
Class A
UL62368-1,
CE EN55032/24,
FCC Class A
CB,
CE EN55032/24
Class A
* All specifications are subject to change without notice.
Product Features
Front/Rear Panel Description (1U 20A Models)
Switched Metered by Outlet/ Metered by Outlet/ Switched/ Monitor Series
Source Status Indicator - Indicates the status of Source A and B.
Source Selected Indicator - Indicates Source A or B is in use.
Output Indicator - Indicates the output is available or not.
Status Indicator - Indicates the condition of the ATS PDU (eg. load or
environment status).
Multifunction LCD Readout - Displays various ATS PDU information such as
power and load condition.
Ethernet Port – Used to connect ATS PDU to the network.
ENVIROSENSOR/ Daisy Chain (In) Port (RJ45 modular port) – Used for
ENVIROSENSOR or chaining to previous ATS PDU.
USB Port - Used to upgrade the firmware via a flash drive.
Serial Port (RJ45 modular port) - Used to connect to a PC and control the
ATS PDU locally via SSH/Telnet.
Daisy Chain (Out) Port – Used for chaining to next ATS PDU.
Select Button - Used to control the LCD screen and toggle through the
available information options.
Enter Button - Used to choose selected items, enter to next level menu or
return to previous menu.
AC Inlet/AC Power Cord - Use to connnect ATS PDU to utility or UPS.
Ground Stud - Use to ground the ATS PDU.
AC Output Receptacles - Provides power distribution for connected
equipment.
Outlet Indicator (switched series only) - When the LED is on, the outlet is
providing power to connected equipment
Circuit Breaker – Provides output overload protection.
1
2
3
4
5
6
7
8
9
10
M
N
Q
P
O
- Critical
- Warning
- Normal
Link
Tx/Rx
In /
ENV
U
SB
Out
Serial
Enter
Select
A
B
C
L
J
I
K
A
B
D
E
F
G H
- Critical
- Warning
- Normal
USB
Serial
Enter
Select
A
B
C
L
I
K
A
B
D
E
H
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.