EXPERT WW   rev.12

EXPERT WW

6.7.  Cool Cell

The  controller  can  control  one  cool  cell 
output. This cooling system reduces the air 
temperature by evaporation of water into the 
air stream.

Operating Diagram of 

a Cool Cell Output

Cool Cell 

Output

T° 

(inside or 

outside)

Off T°

Off

On

On T°

Principle of operation: 

The cool cell output 

can  either  operate  according  to  the  inside 
temperature or outside temperature: it starts 
running  in  timer  mode  when  the  inside  (or 
outside)  temperature  rises  and  reaches  the 
output’s start temperature; the output stops 
when temperature falls below a user-defined 
value. It can also stop when humidity levels 
are too high (see RH Compensation in chap-
ter 10). 

Start/Stop  Temperatures: 

If  the  cool  cell 

output operates according to the inside tem-
perature, its start and stop temperatures are 
related to the set point; this means they are 
automatically  adjusted  when  the  set  point 
changes. That is not the case if cool cells op-
erate according to the outside temperature.

Operating Time Range: 

The user can specify 

a time range during which the cool cell output 
can run. This allows deactivating the output 
at night for instance.

Cool Cell LED:

 The cool cell LED located on 

the faceplate of the controller tells the status 
of cooling cycles:

LED is Off:   the cool cell output is off
LED is On: 

 

the cool cell output is on

Settings

1. Select:

  Main menu 

  Start/Stop*
  Cool Cell**

*  A password may be required to access this menu.
**  This menu is accessible if the cool cell output is 

enabled in the Installation Setup (section 4.5).

Cool Cell Settings

 

Use   to navigate

Temperature 

Inside

On  Temperature 

85.0 °F

Off Temperature 

83.0 °F

On  Time 

15 sec

Off Time 

900 sec

Start at 

6:00A h:m

Stop at 

9:00P h:m

2. Set the following parameters:

Temperature —

 Select 

“inside”

 if the opera-

tion of cool cells is based on the inside tem-
perature; select 

“outside”

 if it is based on the 

outside temperature. 

On  temperature  —

  Select  the  temperature 

(inside or outside T°) at which the cool cell 
output starts.

Off  temperature  —

  Select  the  temperature 

(inside or outside T°) below which the cool 
cell output stops.

On & Off times —

 Set the 

“On & Off Times”

 of 

the cool cell timer. 

Start & stop at —

 Specify the period of time 

over which the output can run.

6.8.  Misting Output

The controller can control one misting output. 
When the room temperature reaches the start 
temperature  of  the  output,  mist  units  are 
activated and run in timer mode according to 
their minimum timer (Min On Time & Min Off 
Time). Then, as temperature rises, a gradual 
transition is made from the minimum timer 
towards the maximum timer (Max On Time  & 
Max Off Time). The second mist timer is fully 
used when the room temperature reaches the 
Maximum  Temperature    parameter  setting. 
The  misting  output  is  disabled  when  the 
temperature falls below a user-defined value. 
It can also stop when humidity levels are too 
high (see RH Compensation in chapter 10).

On Time 2

or 

Off Time 2

On Time 1

or 

Off Time 1

OFF

Mist 

Timer

Misting

Output

ON T°

Max T°

OFF T°

 

Start  /  stop  temperatures: 

Operating  tem-

peratures  of  the  mist  output  can  either  be 
related to the set point – which means the 
controller automatically adjusts them when 
the set point changes – or they can be set 
as absolute values. Refer to the Installation 
Setup chapter to choose if the output follows 
the set point or not (sec. 4.5). 

Operating  time  range: 

You  can  specify  a 

period of time over which the mist output is 
allowed to run. This allows deactivating the 
mist output at night for instance. 

Mist  LED:

  The  Mist  LED  located  on  the 

faceplate of the controller tells the status of 
misting cycles:

LED is Off:  The mist output is off
LED is On:  The mist output is on

Содержание EXPERT WW

Страница 1: ...EXPERT WW Temperature controller User s Manual...

Страница 2: ...f this product is used in a manner not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is howev...

Страница 3: ...Operation 18 5 3 2 Settings 18 5 3 3 Modifying Curve Points 18 6 VENTILATION COOLING 19 6 1 Minimum Ventilation 19 6 1 1 Minimum Ventilation Cycles 19 6 1 2 Minimum Vent Settings 19 6 1 3 Minimum Ven...

Страница 4: ...l Age Count 41 12 5 Automatic Reminder 41 13 TECHNICAL SPECIFICATIONS 42 14 MEMORY CARD 43 14 1 Principle of Operation 43 14 2 Accessing the Transfer Menu 43 14 3 Configuration Transfer 43 14 3 1 Inst...

Страница 5: ...ontroller is located must always remain between 32 F and 104 F 0 C to 40 C Indoor use only To avoid exposing the controller to harmful gases or excessive humidity it is preferable to install it in a c...

Страница 6: ...y Menus History menus allow monitoring the sensor readings and verify the run time of some out puts The controller comes with the following histories menus Minimum maximum sensor readings Ambient temp...

Страница 7: ...ect the devices to the 0 10V outputs This type of output can be used to connect various devices such as heat mats or fans 3 USER INTERFACE 3 1 Location of the Controls Menu selectors Use these buttons...

Страница 8: ...natural ventilation curtain 2 is opening Close Solid LED natural ventilation curtain 2 is closing CURTAIN 1 Open Solid LED natural ventilation curtain 1 is opening Close Solid LED natural ventilation...

Страница 9: ...user 2 pass word is posted the prompt Change Password appears on screen Use the adjustment buttons to set the new password code 4 Use the adjustment buttons to confirm the new installer password then...

Страница 10: ...at are enabled in the Installation Setup are available see sec 4 5 The day number refers to the animal age 4 3 2 Copying Pasting Programs Use the copy paste function to duplicate all parameter setting...

Страница 11: ...of temperature 2 Potentiometer Pot The vent door inlet reaches predefined positions with the help of a potentiometer as a function of temperature Only the first vent door inlet output can use a potent...

Страница 12: ...able the proper type of panel RP 16 or RP 32 This parameter is common to all programs Use age based functions Some functions of the controller are based on the age of the ani mals temperature curve co...

Страница 13: ...probe Select the number of inside temperature probes that are connected to the controller 1 to 8 probes Inside relative humidity RH probe Select Yes if an indoor humidity probe is connected to the con...

Страница 14: ...ly outputs that are enabled in the Setup menu are available sec 4 5 1 2 3 4 5 6 7 8 9 10 TMR Fan Stage 6 Relay Assignment 2 Select a relay then set its status as fol lows The relay is assigned to the...

Страница 15: ...ers op erate according to the clean mode set point heaters turn on when the room temperature is lower than the clean mode set point Refer to section 5 1 to adjust the clean mode set point Low temperat...

Страница 16: ...te tempera ture changes and to verify the controller s performances When the test is enabled all outputs of the controller operate according to the simulated temperature 1 Select Main menu Setup Test...

Страница 17: ...oup starts being used Note that the 1st group automatically starts in minimum ventilation or at stage 1 if minimum ventilation is not used Also note that the controller automatically limits the stage...

Страница 18: ...sec 5 3 3 Status Select Yes to activate the curve Once the curve is on the controller auto matically adjusts the set point automatically between consecutive points of the curve for this reason curve...

Страница 19: ...ilation curve is composed of 10 steps and each step associates an On Time with an animal age Once the curve is enabled the controller changes On Time portion of the minimum ventilation cycles every ho...

Страница 20: ...oint A to point B up to full operation of the fans when the set point differential is reached when the Off Time becomes less than 15 seconds it is fixed at 15 seconds until the temperature has reached...

Страница 21: ...is enabled in the Installation Setup section 4 5 0 10V Output Ventilation Use to navigate Mode Automatic Current output 100 Start temp 70 0 F Min 40 Max 100 Max Output at 72 0 F Stop at 69 5 F 2 Set...

Страница 22: ...al ventilation is disabled when the aver age temperature decreases of 5 F 2 8 C below the curtain s closing temperature or when tunnel ventilation starts see graph below Transition from tunnel to natu...

Страница 23: ...he tunnel door operates according to the room temperature the door reaches the posi tion associated with the 1st tunnel stage when the controller enters in tunnel ventilation The controller then start...

Страница 24: ...by 4 for every 1 F 0 6 C in the compensation interval i e an interval of 3 F means a 12 increase The curtain s Off Time is decreased by the same amount Compensation interval Outside T Set Point Curre...

Страница 25: ...s linked with the activation of a user defined fan stage when the start temperature of that fan stage is reached the controller starts controlling tunnel doors according to the static pressure level I...

Страница 26: ...re is optional and can only be used if age based functions are enabled in the Installation Setup section 4 5 Minimum outside temperature A minimum outside temperature can be specified to avoid enterin...

Страница 27: ...ventilation see Installation Setup in section 4 5 Minimum outdoor temperature Select the outside temperature below which both tunnel doors remain closed Available if an outside temperature probe is en...

Страница 28: ...e points of ventilation stages are defined the user can specify the temperature at which vent doors inlets reach their over opening position Start T of the last stage over opening bandwidth Closing Ve...

Страница 29: ...u see section 4 11 Closed This is the position of the vent door inlet during the Off Time portion of minimum ventilation cycles Set this position to the desired value Stage x Assign a vent door inlet...

Страница 30: ...he vent door inlet closes according to the same cycle 6 5 2 2 Vent Door Settings 1 Select Main menu Vent Inlet Vent door Inlet 1 is already displayed This menu is accessible if at least one vent door...

Страница 31: ...sure level exceeds the high or low static pressure set point vent doors inlets wait for the end of the Wind Effect Delay before moving They will only move if the high or low pressure condition is stil...

Страница 32: ...Automatic Manual You can manually control the opening of a 0 10V output by using the manual control mode While this mode is used the control ler stops controlling the output and lets you choose the i...

Страница 33: ...ollowing parameters Temperature Select inside if the opera tion of cool cells is based on the inside tem perature select outside if it is based on the outside temperature On temperature Select the tem...

Страница 34: ...the set point changes 1 Select Main menu Start Stop Heaters Heaters Start Stop Use to navigate Heater 2 Lo fire On 71 0 F Off 73 0 F Hi fire On 70 0 F Off 73 0 F Heater 1 Lo fire On 73 0 F Off 75 0 F...

Страница 35: ...to stay lit all day long select No to use light cycles Maximum Intensity If the lights on 24 hours option is enabled above set the maxi mum light intensity to the desired value This parameter is acces...

Страница 36: ...PUTS The controller has 2 outputs to control various devices using the real time clock These clock output can use up to 12 timer cycles A clock output starts when the On Time of a timer is reached it...

Страница 37: ...dition a password may be required to access this menu section 4 2 RH Compensation Use to navigate RH Set Point 65 Heater Compensation Min On Time 15 sec Max On Time 45 sec Cycle Time 300 sec Mist on L...

Страница 38: ...ds an alarm when the temperature falls below low alarm limit that is associated to the clean mode The low alarm limit used in clean mode is re lated to the clean mode set point this means the alarm li...

Страница 39: ...mit Specify the maximum amount of water that can be consumed by each water meter per 15 minutes 1 10 000 gal or liters 15 min This parameter is accessible if a water meter is enabled sec 4 7 1 Static...

Страница 40: ...tside temperature probes for the past 75 days This parameter is accessible if an outside temperature sensor is enabled section 4 7 1 Inside relative humidity RH This menu contains the daily minimum an...

Страница 41: ...culled marketed At the beginning of a group the user must specify the initial number of animals Afterwards the user can specify the number of mortalities culled and marketed animals as it occurs ALL h...

Страница 42: ...input 4 20 mA Outside RH input 0 2 5Vdc Temperature inputs 1K 77 F 25 C NTC Relays 1 20 Dry contact 15 A RES 50 60 Hz 16 FLA 120 VAC 1HP 746 W 12 FLA 240 VAC 2HP 1490 W Max tungsten light bulb 8 3A 1...

Страница 43: ...component of the configuration without affecting the two other components For instance you can upload new controller software without affecting your calibration parameter settings 14 3 1 Installing a...

Страница 44: ...NEXT 3 Read the warning message carefully then press Next 4 Select the proper firmware file fir on the main screen The icon indicates which files can be used for the transfer FIRMWARE UPDATE Select Ex...

Страница 45: ...19 Settings 19 Set point curve Curve offset 18 Enable the curve function 12 Principle of operation 18 Settings 18 D Date 9 Day Night Activation 15 Day night times 15 Night set point Principle of oper...

Страница 46: ...s Current probe set in use 40 Principle of operation 26 Probe assignment 14 Settings 27 Programs Automatic program switch Activation 12 Settings 9 12 Copy paste program settings 10 Current program in...

Страница 47: ...ion 25 26 27 Probe set 2 27 Settings 27 Tunnel doors following natural curtains 11 Tunnel Natural vent transition 23 U Units 10 User password See Password V Vent door inlet potentiometer Activation 11...

Отзывы: