35

Address Description 

Default 

 

defined by configuration.

 

 

1.8: Users/Permissions   

Address Description 

Default 

 

P20E 

 

User can view memory

 and status - If this option is off, user 

cannot enter memory view mode, statuses and active time 
zones.

 

Enable 

P21E

 

User can change his code

 - 

If a User has this option on

 ,he is 

considered as a super user that means the menu of user mode is open 
 

User 1 only  

 P22E

 

User can change all codes

 - 

If a User has this option on, user 

can access User Programming Mode and change All User code 
numbers.

 

User 1 only  

P23E

 

User can allow access to installer mode

 - 

If a User has this 

option on, access to Installer Program Mode is only possible by 

entering the installer code, and after that, the code of this User. 
To use it, option "Direct access for installer to programming 

mode" 

[P313]

 should be switched to off in User Mode.

 

User 1 only 

Available on 
User Mode only

 

P24E

 

User can change phone or address

 - 

If a User has this 

option on, user can access User Programming Mode and change 
the telephone and call divert numbers.

 

Enable 
User 1 only 

 P25E

 

User can change the clock

 - 

If a User has this option on, user 

can access User Programming Mode and change the Time & 

date settings 

and set daylight saving time.

 

Enable 
User 1 only 

P26E

 

User can learn radio devices

 - 

If a User has this option on, 

user can access User Programming Mode and Learn a new 

Radio Key or Wireless Zone Device. The user can also remove 
radio devices or find what location number a device is stored at.

 

User 1 only 

 

1.9 Users/Pendants   

Address Description 

Default 

 

P27E 

 

Learn pendant - 

Save new pendant in memory

pressing on 

Pendant's panic Button will be used for learning  operation   

Disable 

P28E

 

Find pendant

 -

 Find existing pendant in memory

 

Disable 

 P29E

 

Delete pendant

 -

 Delete existing pendant from memory

 

Disable 

P30E

 

Pendant can disarm during alarm only

 -

 If this option is on, 

pendant can disarm the alarm during alarm only. If this option 

is off, the pendant cannot disarm the panel in any state.

 

Disable 

P31E

 

Pendant can disarm during entry delay only

 -

 If this option 

is on, pendant can disarm the alarm during alarm only. If this 
option is off, the pendant can disarm the panel in any state.

 

Disable 

P392E 

Pendant Panic Alarm to Output - 

A Pendant Panic Alarm can 

be assigned to an Output or multiple Outputs. This can be used 

to operate an audible or visual alarm connected to the Output

 

 Outputs 

1,2,11-16 

Содержание serenity

Страница 1: ...ELECTRONIC ENGINEERING LTD Serenity CONTROL PANEL Technician s Handbook Note this is a draft version...

Страница 2: ...nic Engineering Ltd reserves the right to revise this publication and to make changes to its content at any time without obligation to notify any person or entity of such revision changes These materi...

Страница 3: ...ons and symbols description 10 Table 3 Alarm Trouble Graphic Symbols 11 Using Keypad Helpful Tips 13 Control Panel Programming Types Local Configuration Mode 15 Quick Programming Mode 17 Installer Pro...

Страница 4: ...ide This Installation manual is a part of manuals set Please refer to technician manual for configuration of the panel 1 Warnings This product is designed for indoor use only Read carefully all manual...

Страница 5: ...r wired Zone 31 Zone 32 5 Zone 32 wire connection 6 Wire connection for Output 3 7 Wire connection for Output 2 8 Positive 12V voltage output for external devices 9 Negative 12V voltage output for ext...

Страница 6: ...6 Lift the two notches located on the both sides of the bracket Remove the bracket from the panel Connect wires into terminal blocks according configuration requirements see Connection Diagram and scr...

Страница 7: ...t Screw the bracket to the panel 4 Rear View 1 USB Port USB cable supplied 2 Wireless Radio Module 3 Internal Piezo Sounder 4 RFID Module 5 Battery Connector 6 NI MH battery Back up supplied 7 Wires c...

Страница 8: ...panel buttons and select from the drop list the required programming mode then use the buttons on the touch panel screen see picture 1 picture 2 to search the required menu and to define the system s...

Страница 9: ...key The A key used for ARM pre programmed The B key used for zone bypass action pre programmed 1 The C key used to enter to memory display pre programmed 2 Can be used to check all boxes for specific...

Страница 10: ...touch button ARM OR DISARM Touch Button and Disarm status indication light Alarm troubles status display Touch Button and Warning alert indication ESC or EXIT touch button View of A B C and D keys fun...

Страница 11: ...der to perform the commands customization list installer has two options 1 Programming Mode Keypads Control Menu see on page 12 how to access to programming mode 2 Using command Address P113E see desc...

Страница 12: ...Battery panel CAN BUS Fail Ethernet Fail GSM GPRS Fail Communication Fail Panel Tamper RF Jamming Radio Zones Low Battery Pendant low battery AREA is not ready the number 1 indicates AREA number 1 Zon...

Страница 13: ...the keypad has been pressed Triple beeps For ARM DISARM WARNING STAY operations Long beep For alarms warning corresponded configuration parameters Slow beeping At arming start exit delay and warning e...

Страница 14: ...lect Bypass Zone Number 1 2 Option 1 Installer can use the buttons or to move between output numbers Option 2 Installer can use the Keypad keys to move between output numbers by typing the output numb...

Страница 15: ...isarmed state will immediately start the arm procedure Presenting the proximity tag once again will DISARM the system Installer must note that ARM DISARM functions are not enabled by default but if in...

Страница 16: ...anel screen 2 Use the button to scroll down until the desired option local Configuration mode is displayed Note The Arm area 1 is displayed by default each of the other areas options should be display...

Страница 17: ...ion summary table section in this manual you can easily find the command description by using the Command number which appears in command number column in this page Note if this level is used for the...

Страница 18: ...2 21 User names 1 4 22 User codes 1 4 23 Learn Pendant user 1 4 24 Learn user 1 4 Access tag 25 User 1 4 assigned to area 1 26 User 1 4 assigned to area 2 27 User 1 4 assigned to area 3 28 User 1 4 as...

Страница 19: ...19 3 Press on the Enter button 4 Insert the installer password and press on the Enter button 5 Use the touch button to move through all Quick programming menu...

Страница 20: ...r Note Default installer password is 6 zeros 000000 1 Insert the installer password and press on the enter button 2 Use the buttons to select the required function and programming level 4 User Program...

Страница 21: ...rogramming Enter Insert User Code 1234 End User Permissions Programming Default permissions for User 1 1 Users User setting select User code 1 64 User 1 code 1234 User name 1 64 Time zone assignment U...

Страница 22: ...1 16 User assignment User 1 64 controlled by time zone 1 8 5 Zones Radio zones Learn radio zone 1 32 Find radio zone Delete radio zone 1 32 6 Report channels Settings channel 1 8 phone number 7 Commun...

Страница 23: ...equence or can select specific requested steps according the installation type Note By default there are no detectors assigned or learned in the control panel so any attempt of arming the system will...

Страница 24: ...els 3 4 5 voice message PSTN channel 6 TCP IP channel 7 voice message GSM and channel 8 ContactID GSM see Description P200E Voice Message GSM Set channel type as Voice Message GSM Need to set GSM IP e...

Страница 25: ...6 characters 2 All other protocols 4 characters 3 You can use the characters 0 9 B C D E F 4 You don t need an ACC number When channel is programmed as Voice message SMS protocol All Zeros A letter n...

Страница 26: ...ne to Area If a Zone is assigned only to one area it will activate if specified area is armed If zone assigned to more than one area it will activate only when all assigned areas are armed By default...

Страница 27: ...ion Up to 8 digits Disable Step 21 Walk Test Address Description Default P343E Walk Test This address is used to start walk test mode while in installer or user program mode By walking past all of the...

Страница 28: ...SMOKE Zone Config screens Important Notice 1 Setting or changing of Zone Configuration will be implemented into the detector configuration in the next event such as Open Zone Open Tamper supervision...

Страница 29: ...29...

Страница 30: ...rmissions 34 Pendants 34 Access Tag 35 OUTPUTS Settings 36 Output Type 37 User Assignment 37 Time Zone Assignment 37 Keypad Assignment 38 Signals to Output 38 Timing 39 Radio Output 39 Output Name 40...

Страница 31: ...7 KEYSWITCH Settings 47 Options 47 CLOCK TIMERS System Date and Timers 48 Date Format 48 Timers 48 Delays 49 ZONES Status 49 Area Assignment 50 Working Mode 50 Options 51 Zone Response Time 51 Alarms...

Страница 32: ...tions 58 COMMUNICATIONS Remote Access 60 Phone Line Options 61 PSTN 61 GSM 62 TCP IP 62 CUN BUS 62 Contact ID Codes 63 SIA Codes 63 Voice Message Numbers 63 Control Code Number 64 MISCELLANEOUS Chime...

Страница 33: ...nt via the dialler If Latchkey Mode is armed and a user with this option off disarms the alarm a disarm report will be sent to alert parents when their children have returned home Reporting of Latchke...

Страница 34: ...he Output or it can be turned off by the same user or by a different user with the next program location Disable P16E User code turns output off Any user can be allowed to turn an Output OFF This Func...

Страница 35: ...User has this option on user can access User Programming Mode and change the Time date settings and set daylight saving time Enable User 1 only P26E User can learn radio devices If a User has this opt...

Страница 36: ...If you wish to delete a single Access Tag or Card entering P35 and user number while in Program Mode will delete the stored code against that user Disable P36E Access tag can arm If this option is on...

Страница 37: ...state It is designed to keep audible alarms silent when the full system disarm but part of alarms like Panic or Fire alarm still turns audible alarms to on regardless of this setting Enable P43E Disab...

Страница 38: ...ram location Disable P1016E User code turns this output off Any user can be allowed to turn an Output OFF This Function can be used to control external devices via the panel keypad with a User assigne...

Страница 39: ...arm to an Output A Sensor Watch alarm occurs when a detector has not operated within a set period of time Disable P17E Duress Alarm to Output Duress Alarm P311 can be assigned to an Output or multiple...

Страница 40: ...st outputs endless P63E Output Chime Time The Chime Mode time affects the time the output turns on when a Chime Zone is activated The Chime time is in 1 10th second increments so that very quick timin...

Страница 41: ...a Near Alarm report to the monitoring station If no further alarms occur within 45 minutes the near alarm timer is reset and a restore is sent for the zone that activated If the zone that activated is...

Страница 42: ...Area 1 See comments 3 3 Areas User Assignment Address Description Default P1014E User Assigned To Area If a User has this option on they can Arm Disarm all zones assigned to Area all users assigned t...

Страница 43: ...Output Each Area can have a separate indication assigned to a different output if required Outputs 11 16 only P79E Disarm Indication to Output For monitoring purposes a Disarm indication can be assign...

Страница 44: ...e will be applied to selected output e g siren indicating arming Disable P88E Disarm Pulse to Output A single pulse will be applied to output e g siren indicating disarming Disable P89E Stay Disarm Pu...

Страница 45: ...keypad was not touched Disable 4 1 Keypads Area Assignment Address Description Default P97E Keypad Assigned To Area This option assigns keypad to area For example if keypad is assigned to only area 1...

Страница 46: ...hich is control panel keypad P102E Wrong Code Alarm to Output If someone is attempting disarm the alarm by trying various code combinations and they enter in 5 wrong codes the panel will go into a Wro...

Страница 47: ...keypads will sound their buzzers when Medical Alarm is activated Enable For all Keypads P111E Wrong Code Beeps Keypad Buzzer If someone enters in an incorrect code more than 4 times the alarm can be...

Страница 48: ...oggle its current state I e if armed it will become disarmed or vice versa If this option is turned off it is assumed that the key switch is a latching type This means that when the key switch is oper...

Страница 49: ...econds 20s 6 3 Clock and Timers Delays Address Description Default P127E Alarm Reporting Delay seconds If this address is set to 0 there will be no report delay If it is set to any value other than 0...

Страница 50: ...ired Zone 1 2 only P134E Handover zone A Handover Zone is one that its entry delay will apply provided a Non Handover entry zone is triggered first If no other entry delay zones are triggered before t...

Страница 51: ...zone also has an entry delay programmed P174 this delay will apply If the 24 Hour Fire zone activates but then resets before the entry delay expires no alarm will be generated Once the alarm has been...

Страница 52: ...Disable P154E Response of 300 ms Disable P155E Response of 350 ms Disable 7 5 Zones Alarms to Output Address Description Default P156E Zone alarm assigned to output If an Area is Armed and a zone assi...

Страница 53: ...are programmed for near and verified alarms P73 it is also possible to get an indication of a verified alarm from any of the 16 outputs using this program location A verified alarm is the second alar...

Страница 54: ...beeps to keypad If Stay Mode is Armed and a Stay Mode delay zone triggers the entry delay it can also beep the keypad buzzer to warn that the entry delay is counting down and the alarm should be turn...

Страница 55: ...in unlimited alarms for that zone during an armed period but a count of 1 15 will shut down the zone once the programmed count has been reached Disarming the alarm will reset this count In case the z...

Страница 56: ...inishes immediately before midnight 23 59 59 on the programmed date Holidays can be programmed in any order although for simplicity it is recommended that they are programmed in chronological order an...

Страница 57: ...RS Need to set GSM IP enabled to use this type of channel Cannot be set if TCP IP channel has already been selected Default assignment channel 1 SIA PSTN channel 2 ContactID PSTN channel 3 voice messa...

Страница 58: ...nnel This option is used to activate deactivate a channel Disable P202E Phone Number or Server Address Can be up to 8 phone numbers for channels defines as PSTN GSM Voice SMS or 8 server addresses for...

Страница 59: ...y Low Enable P209E Report Communication fail If this option is on the panel will report a Communication fail Channels 3 4 5 7 Off All others On P210E Report System Tamper If this option is on the pane...

Страница 60: ...at P76 a Delinquency Alarm will be sent to the Monitoring Station Channels 3 4 5 7 Off All others On P225E Report Fuse Failure The panel has two on board thermal fuses designed to protect the 12v DC...

Страница 61: ...sarmed if this option is on the Remote access option is allowed only in disarmed state Disable P388E Enable Direct Remote Access This option uses for remote user remote control of the system via strin...

Страница 62: ...rs the call can be set at this parameter Minimal value is 2 for using caller ID detection see also P248E 8 P248E Answering System Defeat The panel can automatically answer an in coming call in two way...

Страница 63: ...racters Disable P260E DNS Server The network DNS server address for defined static IP address up to 16 characters Disable P377E TCP Remote Control Port The TCP IP port number used for remote control a...

Страница 64: ...d is empty system uses default code 5041 PA P270E Fire Alarm SIA Code Set SIA code for fire alarm Code value has to be two letters from A to Z when input field is empty system uses default code 4641 F...

Страница 65: ...This code cannot starts from 0 Used when accessing Serenity remotely Output 1 101 Output 16 116 P299E Turn Output off Control Code The control code value has 1 4 digits This code cannot starts from 0...

Страница 66: ...a value from 1 255 The units are in 1 10th second increments This means that a value of 10 will beep the keypad buzzer for 1 second 10 P1160E Chime zone alarm assigned to output If a zone is programm...

Страница 67: ...not be re armed until the Installer has reset the alarm The Trouble indication will latch on even if the tamper alarm has been cleared until reset by the installer to indicate that lockout is in effec...

Страница 68: ...option is turned on access to view Memory Log Status Window and Active Time Zones while the Serenity is in disarm mode will only be allowed by using an authorized code If this option is turned off any...

Страница 69: ...eypad Control panel number is always 1 You can only change the number of the keypad currently used between numbers 2 8 Note each keypad has its own configurations in the Serenity so if you change a ke...

Страница 70: ...displays the Ethernet module details such as IP address Subnet mask address Gateway address and MAC address xx Disable P348E Manual Test Call This option tests the specified report channel Disable 11...

Страница 71: ...ss of the products for a particular purpose or otherwise which extend beyond the description on the face hereof This limited Warranty Certificate is the Purchaser s sole and exclusive remedy against C...

Страница 72: ......

Страница 73: ...73...

Отзывы: