ELECTRICAL INSTALLATION AND CONTROLS
QUINTA ACE 135 AND 160
GENERAL
The Quinta Ace 135 and 160 is supplied as standard
with electronic control and flame ionisation safety controls,
with a specially designed microprocessor at the heart
of the control system.
SPECIFICATIONS
ELECTRICAL SUPPLY
The Quinta Ace 135 and 160 must have a permanent
230V/50Hz single phase supply rated at 6.3 amps. The boiler is
not phase/neutral sensitive and is completely wired.
CONTROL BOX
•
Manufacture: SIT
•
Model: CU-GH06c
•
Supply voltage: 230V/50Hz
•
Pump run on (HTG): 1-99 minutes
FUSE SPECIFICATION
The boiler is protected by fuses:
•
Main Fuse F1 (230 VAC) 6.3 amps
•
PCU 1.6 amps
•
Fan 230V
BOILER TEMPERATURE CONTROL
The Quinta Ace range has electronic temperature control with
flow and return temperature sensors. The flow temperature can
be adjusted between 20 and 90°C.
HIGH LIMIT TEMPERATURE PROTECTION
The high limit temperature protection device switches off and
locks out the boiler when the flow temperature exceeds the high
limit set point (set by boiler type). When the fault is corrected the
boiler can be restarted by using the reset key on the control panel.
LOW WATER PROTECTION (FLOW AND CONTENT)
The Quinta Ace range is supplied with a low water protection on
the basis of a low water pressure switch and also by temperature
measurement. By modulating down at the moment that the water
flow threatens to fall too low; the boiler is kept operating for as
long as possible.
EXTERNAL CONNECTIONS
All external connections are made to any one of the standard
supplied PCBs depending on the type of control and external
components fitted.
CONNECTING A THIRD PARTY
CONTROL UNIT TO A STANDARD
BOARD CU-GH-06
MAIN PCB (CU-GH06)
Connection PCB (CB-01) is included as standard.
PCB (SCB 01)
This has two potential-
free contacts, status
/ functions can be
configured as required.
Depending on the
setting a particular
status / function can
be transmitted by the
boiler. Either alarm,
run, Boiler on CH,
pump control, etc.
Also suplied as standard is the SCB-01
(part of the new e-Smart platform)
)LJ
6&%3&%
c
N C o
N
Status
c
N C o
N
Status
+
0
0-10
SCB-01
24V DC
Relay Load
10A 250V AC (NO)
8A 250V AC
5A 30V DC
X1
2 3
1
X2
2 3
1
Pump
N
L
X3
2
1
1
1
0
1
9
8
7
6
5
4
2 3
1
On/off
OT
PWM
0
+
0 - 10
0
+
Tout
BL
RL
X4
- 7
1
6.3 AT
F1
X5
- 7
1
X6
- 5
1
1
CB-01
X1
2 3
1
X2
2 3
1
Pump
N
L
X3
2
1
1
1
0
1
9
8
7
6
5
4
2 3
1
On/off
OT
PWM
0
+
0 - 10
0
+
Tout
BL
RL
X4
- 7
1
6.3 AT
F1
X5
- 7
1
X6
- 5
1
1
CB-01
Содержание Quinta Ace 115
Страница 1: ...QUINTA ACE RANGE ...
Страница 70: ......