QUINTA ACE 30 AND 45
ROOM-SEALED, 80/125MM HORIZONTAL
CONCENTRIC FLUE KIT OPTION QP01
For use when the boiler/s are mounted on and flued through a rear outside wall, and for a typical single-boiler installation. It can also be
used for multiple boilers but each must have its own flue system and terminals positioned at a minimum of 530mm centres and never
installed immediately above another. For two boilers only, it is also possible to install the external terminal wall plates touching each other.
Kit parts – MG410082982
(max wall thickness 500mm)
•
1 x horizontal terminal
•
Note: Boiler bend and wall plate are included
HORIZONTAL
FLUE KIT
80/125MM
240mm
Sq.
4 x 5mm
holes
204 Sq
240mm
Sq.
RAL colour 7021/9016
125mm o/d
150(min)600/1000(max)
740/1135mm
4 x 5mm
holes
204 Sq
110mm
50mm insertion length
into mating socket
80mm o/d
95mm
145mm
Clearance hole
for terminal through
wall 130mm
Note: 140mm
diameter, recessed
15mm deep, required
from the surface of
the inside wall to allow
clearance for the bend.
Cut terminal on site to suit wall thickness
Max 1000mm – Min 150mm
Wall closures plate should be fitted to terminal before
passing through hole in wall to ensure correct positioning
Kit parts – MG410081940
(extended version max wall thickness 1000mm)
•
1 x horizontal terminal
•
Note: Boiler bend and wall plate are included
EXTENDED
HORIZONTAL
FLUE KIT 80/125MM
240mm
Sq.
4 x 5mm
holes
204 Sq
240mm
Sq.
RAL colour 7021/9016
125mm o/d
150(min)600/1000(max)
740/1135mm
4 x 5mm
holes
204 Sq
110mm
50mm insertion length
into mating socket
80mm o/d
95mm
145mm
50mm insertion length
into mating socket
HRS room-sealed terminal (80/125mm)
MG410082982 and MG410081940
Note: Fall to boiler ≥ 50mm/Mtr.
Centre line of Flue
180mm (approx)