SUGGESTED
ENGINEERING SPECIFICATION
QUINTA ACE
CONSTRUCTION
The boiler will be a wall-hung type condensing boiler which
may also be installed free-standing on a suitable frame.
The single piece, cast aluminium heat exchanger and other
major components are contained within a sealed air box.
The boiler casing will be complete with a removable front
section for maintenance purposes. Electrical and electronic
controls will be contained within the instrument panel
mounted in the drop-down lower front panel and also the
electrical housing mounted on the inside right hand panel.
HYDRAULIC, GAS AND
FLUE CONNECTIONS
The combined flue gas outlet and combustion air inlet will be
mounted on the top of the boiler, with the flow, return, gas and
condensate connections located at the bottom. The boiler will be
suitable for room-sealed or open-flue applications. The boiler will
be designed for central heating and indirect hot water production
up to four bar. The boiler will be suitable for use on sealed
systems and open-vented installations.
OPERATION
The boiler will be complete with a modulating control system
that limits the maximum difference in temperature between the
heating flow and return and the maximum speed at which the
flow temperature increases. The boiler will be complete with a
pre-mix burner (NG or LPG) with the gas/air ratio control system
controlled internally. An intelligent, advanced boiler control will
continuously monitor the boiler conditions, varying the heat
output to suit the system load. The control will be able to react to
external negative influences in the rest of the system (flow rates
and air/gas supply problems), maintaining boiler output for as
long as possible without resorting to a lockout condition. Should
a negative effect happen in the system, the boiler will reduce its
output and/or shut down (shut-off mode), awaiting the negative
conditions to return to normal before re-starting. The control
cannot override the standard flame safety controls. Standard
frost protection will activate below 7°C with stage one activating
system/shunt pump. Stage two will activate below 3°C with
boiler switching on to 10°C flow.
CONTROLS
The boiler will include an “e-Smart” control platform offering
improved connectivity using the integral MK3 controller.
The controls package will allow the actual and set values to
be read and adjusted on the built-in digital display, which also
provides normal operating and fault code indication. The controls
will come as standard with the following inputs/outputs:
•
0-10V input (flow temperature or output percentage control)
•
DHW temperature input
•
high limit lock out
•
safety/shutdown/release input (blocking)
•
low water protection
•
outside sensor (optional)
•
external shunt pump control
•
service report output
•
external system pump control
•
fault alarm output
•
DHW 3-port valve control or pump
•
OpenTherm, R-Bus & Volt Free Enable connection.
FEATURES
•
Low, Class 6 NO
x
≤36mg/kWh
•
Fully modulating
•
Quiet operation <52dB(A)
•
LED illuminated interior (integral battery)
•
Data file for storing fault/run info
•
Automatic maintenance warning
•
PC connection
•
ErP compliant
•
Relay kit (optional)
•
Premix burner
•
In build passive flue gas non-return valve.
The Quinta Ace 30/45/55/65/90/115 boilers conform with
the following EC-directives:
GAR (EU) 2016/426 to EN 15502-1:2012 +A1:2015 and
EN 15502-2-1:2012 +A1:2016
BED 92/42/EEC to EN 15502-1:2012 +A1:2015 and
EN 15502-2-1:2012 +A1: 2016
EMC 2014/30/EU to EN 55014-1:2017, EN 61000-3-2:2014
and EN 61000-3-3:2013
LVD 2014/35/EU to EN60335-2-102:2016, EN60335-1:2012
ErP 2009/125/EC
CE Certification Remeha Quinta Ace 30/45/55/65/90/115
PIN: 0063CS3928
09
TECHNICAL INFORMATION
AND ENGINEERING SPECIFICATION