45
FLUE
OPTIONS
QUINTA ACE 55, 65, 90, 115, 135 AND 160
ROOM-SEALED TWO ZONE CLV FLUE KIT
The Quinta Ace boiler can be installed in areas with different pressure zones if connected to a C53 flue system.
An integral non return valve is fitted as standard.
Combustion air supply and combustion gas discharge are possible in various pressure zones, semi-CLV systems. With the exception of
coastal areas, the maximum permissible difference in height between the combustion air supply and the combustion gas discharge is 36m.
Kit parts – KT030
•
1 x flue connection – S101626
•
1 x flue terminal – PU001
•
1 x air inlet – PU002
•
1 x condensate drain – MG410085130 x siphon –
MG410081165 x condense adaptor kit – MG41008749
TWO ZONE
FLUE KIT
100/150MM
Note 2: Maximum permitted height difference between combustion air supply and flue gas outlet is 36m.
ROOM-SEALED FLUE DATA
QUINTA ACE
55 100MM Ø
QUINTA ACE
65 100MM Ø
QUINTA ACE
90 100MM Ø
QUINTA ACE
115 100MM Ø
QUINTA ACE
135 100MM Ø
QUINTA ACE
160 150MM Ø
Maximum length (M)
27
16
17
14
40
40
Equivalent length of 45
o
elbow (M)
1.4
1.4
1.4
1.4
1.2
1.2
Equivalent length of 90
o
elbow (M)
4.9
4.9
4.9
4.9
2.1
2.1
Note: Fall to boiler ≥ 50mm/Mtr.