Table 4-6 LVRT and HVRT Parameters (IEEE5147 and Rule21)
LVRT and HVRT Control
IEEE1547
Rule21
Parameter name
Description
Setting Range
(Min,
Default
, Max)
Setting Range
(Min,
Default
, Max)
LVRTModeSetting
0: Disable
1: Enable, no reactive
power output
2: Enable, reactive
power output
(0,
0
, 2)
(0,
2
, 2)
LVRTTripVolt
Threshold value of LOW
voltage trip
(70.0%,
80.0%
,
100.0%)
(70.0%,
88.0%
,
100.0%)
LVRTPstReactive1
The factor LVRT Positive
Reactive Current
(0%,
150.0%
,
300.0%)
(0%,
150.0%
,
300.0%)
LVRTNegReactive1
The factor LVRT
Negative Reactive
Current
(0%,
200.0%
,
100%)
(0%,
200.0%
,
100%)
HVRTModeSetting
0: Disable
1: Enable, no reactive
power output
2: Enable, reactive
power output
(0,
0
, 2)
(0,
1
, 2)
HVRTTripVol
Threshold value of HIGH
voltage trip
(100.0%,
110.0%
,
135.0%)
(100.0%,
110.0%
,
135.0%)