94
3.
Q(U) Curve
:
Q(U) curve mode. Using the curves to set the
reactive power setpoints (See Figure 4-20). The reactive power
compensation changes according to the grid voltage. These
functions are only available for IEEE-1547 grid standards.
Figure 4-20 Q(U) Curve Mode
Capacitive
Q(%)
_
+
Inductive
(QuCurveU2i,QuCurveQ2i)
U(V)
(QuCurveU1i,
QuCurveQ1i)
(QuCurveU1,
QuCurveQ1)
(QuCurveU2,QuCurveQ2)
INSTRUCTION:
The Q(U) curve function is only available for IEEE-1547 grid
standards.