For more details please see the user manual.
WARNING:
High touch current .
Earth connection essential before connecting supply.
1
2
AC Output:
Use 90¡ã
C wire, either 3~2/0AWG copper or
2~2/0AWG aluminum, torque 110 in-lbs.
AC Ground:
Use 90¡ã
C copper wire, 6-4AWG for internal
grounding bar or
external grounding stud, torque 50 in-lbs.
L1
L2
L3
N
AC Output:
Use 90¡ã
C wire, either 3~2/0AWG copper or
2~2/0AWG aluminum, torque 110 in-lbs.
AC Ground:
Use 90¡ã
C copper wire, 6-4AWG for internal
grounding bar or
external grounding stud, torque 50 in-lbs.
L1
L2
L3
N
The dimension limited
of lug terminal
24,5(max)
12
,5(m
ax
)
21
(ma
x)
? 19(max)
? 8(min)
? 11,5(max)
Figure 3-33 AC Output and Ground Cable Connection