77
3. PV Input Mode.
This allows the user to read the inverter
working mode as
“
Independent
" or "
Parallel"
mode. The
inverter is factory set in Independent mode. If this needs to be
set to Parallel contact CPS to have this setting changed.
4. Neutral Line Setting.
This option allows the user to select
“Yes/No” if a neutral conductor has been connected to the
inverter. This setting does not affect the operation of the
inverter. This is for measurement and display purposes only.
When a neutral is installed and “Yes” is selected, the inverter
will display L-N measurements.
6. Communication Setting.
This interface is used to set the
Modbus ID and Baud rate for communication. More
information on this is found in the “Commissioning” section.
7. Time.
Press
or
to select the numerical value, then
press
ENT
to go to next option. e.g.: Year to Month. Finally
Press the
ENT
key to confirm the setting.
8. LCD Contrast Setting.
Press
or
to
increase/decrease the LCD contrast. Press
ENT
to accept
changes.
标题
- +
Figure 4-11 LCD contrast grade Setting