57
Table 3-10 Torque and Conductor Specifications
Connection Point
Conductor Range
Torque Value
AC output terminal block
6-3/0 AWG (CU/AL)
14.25 N-m (126 in-lbs
)
Internal grounding bar
6-4 AWG (CU)
5.65 N-m
(
50 in-lbs
)
External grounding point
6-4 AWG (CU)
5.65 N-m
(
50 in-lbs
)
The maximum acceptable conductor size that may be terminated to the AC output
terminal is restricted based on the compression lug maximum dimensions shown in
Figure 3-34
.
Standard 1-hole Lug
Metric 1-hole Lug
Figure 3-34 Compression Lug (OT Terminal) maximum dimensions
Содержание SCA50KTL-DO/US-480
Страница 2: ......
Страница 6: ......
Страница 53: ...47 Figure 3 24 Bypass Terminal option installed within the Standard wirebox ...
Страница 139: ...133 Figure 10 1 CPS SCA50KTL kW and kVA derating curves of PV input voltage ...
Страница 140: ...134 Figure 10 2 CPS SCA60KTL kW and kVA derating curves of PV input voltage ...
Страница 141: ...135 Figure 10 2 CPS SCA60KTL Reactive Power Capability ...