3.1. Recommendations before Installation
See
Chapter 10
, Technical Data for specification ranges and limits.
Check that the inverter environmental specifications (protection degree,
operating temperature range, humidity and altitude, etc) meet the
requirements of the specific project location.
Make sure that the electric utility grid voltage is within range for the grid
standard chosen.
Ensure that the local electric utility grid authority has granted permission
to connect to the grid.
Installation personnel must be qualified electricians or those who have
received professional training.
Wear and use proper PPE (personal protective equipment) during
installation.
Sufficient space according to
Figure 3-3
and
Figure 3-4
must be
provided to allow the inverter cooling system to operate effectively.
Install the inverter away from flammable and/or combustible substances.
Avoid installing the inverter in locations that exceed the temperature
limits specified for the inverter to prevent undesirable power loss.
Do not install the inverter near an electromagnetic source which can
compromise the normal operation of electronic equipment.
NOTICE:
The allowable ambient temperature range for the
SCA50KTL-DO/US-480 and SCA 60KTL-DO/US-480 inverters is
defined based on the following conditions;
Condition 1: -40°C to 70°C, Inverter not installed, and in storage (in
packaging or unpackaged).
Condition 2: -30°C to 60°C, Inverter installed, connected to electric
utility grid and operating during daylight hours.
Condition 3: No low temp limit to 70°C, Inverter installed, connected to
electric utility grid but non-operating (daylight or nighttime hours).
Содержание SCA50KTL-DO/US-480
Страница 2: ......
Страница 6: ......
Страница 53: ...47 Figure 3 24 Bypass Terminal option installed within the Standard wirebox ...
Страница 139: ...133 Figure 10 1 CPS SCA50KTL kW and kVA derating curves of PV input voltage ...
Страница 140: ...134 Figure 10 2 CPS SCA60KTL kW and kVA derating curves of PV input voltage ...
Страница 141: ...135 Figure 10 2 CPS SCA60KTL Reactive Power Capability ...