− 7 −
Operating Procedure
3. Operating Procedure
■
Procedure
1. Inserting Batteries
The Gas Detector is delivered without batteries inserted. Refer to pages 20 to insert the provided
batteries.
2. Turning Gas Detector ON
→
Warming Up
→
Displaying Gas Concentration
Screen
(1) Press the POWER switch. The buzzer will beep and the Gas
Detector will be turned ON.
(2) The LCD main screen will display Adj and the bar graph will
count down while the Gas Detector is warming up. The LCD
sub screen will display Time.
(3) When the sensor is stabilized, the buzzer will beep and the
gas concentration screen will be displayed.
WARNING
Be sure to place the connected gas sampling hose in clean air when
turning ON the Gas Detector. Zero calibration is done automatically.
The wrong gas concentration will be displayed if zero adjustment is
done in gas atmosphere.
WARNING
Be sure to conduct a daily inspection before
performing detection work (see page 21).
CAUTION
Even after displaying the gas concentration screen, zero indication
might be unsettled and flash. In that case, wait for three minutes and
conduct zero adjustment (refer to page 9).
Note
If an error message is displayed, refer to Error Messages on page 18.
Procedure
1
Insert
the
batteries.
2
Turn ON
t he Ga s
Detector.
Displays the gas
concentration
screen.
Warms
up.
3
Detects
4
Turn OFF the
Gas Detector