Alarms
If the machine detects a fault, corresponding information appears in a pop-up window. Additionally, a
warning symbol appears in the standard view's upper right corner, if one or more problems remain.
The following alarms can appear. Recommended corrective action is also given for each alarm.
Alarms
Action/advice
On or more slaves not responding
This alarm appears when the machine is used as
master in a network that has lost contact with one
or more of its slave machines. If this alarm appears,
check all system cables and the power supply to all
machines. When communication has been re-
established, the alarm disappears automatically
again.
Ambient temperature too high!
The machine has switched off all heaters due to too
high ambient temperature (above 35 degrees
Celsius). If continuous fan is selected, the fan
continues to run. The machine resumes operation
automatically if the temperature drops.
Fan control error
The fan speed deviates from the expected fan
speed. If the alarm remains, contact a service
technician.
No contact with internal control
board
Internal fault. If the alarm remains, contact a
service technician.
Internal sensor fault Temp and RH
sensor
Internal fault. If the alarm appears after the
machine has been disassembled, the fault may be
because the sensor connection to the cover has not
been installed correctly. If not, and if the alarm
remains, contact a service technician.
External Temp and RF sensor fault
The machine has lost contact with the external
temp and RH sensor(s). Check that the cables are
correctly installed. When contact with the external
Setpoint RH 60 %, start drying
Hysteresis
5 %
Stop drying = RH 55 %