Heatsink
#6-32 Mounting Screws
Dry Film Interface Pad
Xenus Plus Drive
Blue Protective Sheet
(Discard)
Clear Protective Sheet
(Discard)
HEATSINk & FAN CONFIGURATIONS
HEATSINk MOUNTING
A dry-film interface pad is used in place of thermal
grease. The pad is die-cut to shape and has holes
for the heat sink mounting screws. There are two
protective sheets, blue on one side and clear on the
other. Both must be removed when the interface pad
is installed.
STEPS TO INSTALL
1. Remove the blue protective sheet from one side
of the pad and place the pad on the drive. Make
sure that the holes in the pad align with the holes
on the drive.
2. Remove the clear protective sheet from the pad.
3. Mount the heatsink onto the drive taking care
to see that the holes in the heatsink, pad,
and drive all line up.
4. Torque the #6-32 mounting screws to 8~10 lb-in
(0.9~1.13 N·m).
NO HEATSINk
NO FAN
NO HEATSINk
WITH FAN
LOW-PROFILE HEATSINk
NO FAN
LOW PROFILE HEATSINk
WITH FAN
STANDARD HEATSINk
NO FAN
STANDARD HEATSINk
WITH FAN
NOTE: FANS ARE NOT INCLUDED
WITH HEATSINkS OR HEATSINk kITS