HEATSINk & FAN CONFIGURATIONS

HEATSINk MOUNTING

A dry-film interface pad is used in place of thermal 

grease. The pad is die-cut to shape and has holes 

for  the  heat  sink  mounting  screws.  There  are  two 

protective sheets, blue on one side and clear on the 

other. Both must be removed when the interface pad 

is installed.

STEPS TO INSTALL

1. Remove the blue protective sheet from one side 

of the pad and place the pad on the drive. Make 

sure that the holes in the pad align with the holes 

on the drive.

2. Remove the clear protective sheet from the pad.

3. Mount  the  heatsink  onto  the  drive  taking  care 

to  see  that  the  holes  in  the  heatsink,  pad,

 

and drive all line up.

4. Torque the #6-32 mounting screws to 8~10 lb-in 

(0.9~1.13 N·m).

NO HEATSINk

 

NO FAN

NO HEATSINk

 

WITH FAN

LOW-PROFILE HEATSINk

 

NO FAN

LOW PROFILE HEATSINk

 

WITH FAN

STANDARD HEATSINk

 

NO FAN

STANDARD HEATSINk

 

WITH FAN

NOTE: FANS ARE NOT INCLUDED 

WITH HEATSINkS OR HEATSINk kITS

Содержание Xenus Plus CANopen XPL Series

Страница 1: ...Vac Ic Ip XPL 230 18 100 240 6 18 XPL 230 36 100 240 12 36 XPL 230 40 100 240 20 40 Add R for resolver feedback option Control Modes Indexer Point to Point PVT Camming Gearing Position Velocity Torqu...

Страница 2: ...n LO 2 3 Vdc Vin HI 2 7 Vdc Vhysteresis 400 mVdc Differential IN3 4 or IN5 6 Vin LO 200 mVdc Vin HI 200 mVdc Vhysteresis 200 mVdc IN7 14 Opto isolated 15 30 Vdc compatible bi polar 2 groups of 4 with...

Страница 3: ...drive without heatsink 3 1 lb 1 40 kg for XPL HS heatsink 1 86 lb 0 84 kg for XPL HL heatsink Ambient temperature 0 to 45 C operating 40 to 85 C storage Humidity 0 to 95 non condensing Contaminants Po...

Страница 4: ...nating resistors 18 M counts sec post quadrature 4 5 M lines sec As Emulated Output Quadrature encoder emulation with programmable resolution to 4096 lines 65 536 counts per rev from analog sin cos en...

Страница 5: ...lap LED color may be red green off or flashing of either color CAN status LED 6 9 1 5 D Sub 9F 3 3 2 2 1 8 CAN_L CAN_GND CAN_H CAN_L RJ 45 CAN_GND CAN_H 7 1 J7 Pin 8 Pin 1 canopen connectors Dual RJ 4...

Страница 6: ...e ASCII Interface to Enable the amplifier in Programmed Position mode Home the axis Issue a series of move commands while monitoring position velocity and other run time variables Additional informati...

Страница 7: ...ut diodes the control core will be able to control the on off state of the PWM outputs safe torque OFF STO functional diagram In order for the PWM outputs of the Xenus Plus to be activated current mus...

Страница 8: ...d from devices with active pull up and pull down to take advantage of the high speed inputs Single ended PWM Direction Single ended 50 PWM differential 50 PWM differential PWM Direction Single ended p...

Страница 9: ...ck cable that could occur if the motor encoder had to drive two differential inputs in parallel each with it s own 121 ohm terminating resistor Secondary Encoder Input Input Output Select MAX3032 MAX3...

Страница 10: ...B Quad encoder inputs for Position or Camming modes differential single ended 12 Vdc max 12 Vdc max NON ISOLATED digital INPUTS Inputs IN1 2 are 24V tolerant These are high speed types with pull up r...

Страница 11: ...99k 5 1V IN9 5 4 99k 5 1V IN10 6 24V opto isolated digital INPUTS These inputs have all the programmable functions of the GP inputs plus opto isolation There are two groups of four inputs each with it...

Страница 12: ...riving PLC inputs that are opto isolated and connected to 24 Vdc The diode prevents conduction from 24 Vdc through the 1 k resistor to 5 Vdc in the drive This could turn the PLC input on giving a fals...

Страница 13: ...ange of 10V to 13 2V 5V output 400 mA Signal Ground 21 20 17 5 19 Sin Sin Cos Cos Inx Inx 18 1 10k 121 J10 10k 121 Encoder FG sin cos 5V 0V 23 22 10k 121 indx Frame Ground 10k Sin Cos Indx 10k 10k ANA...

Страница 14: ...SI in the use of clock and data signals but which also supports analog sin cos channels from the same encoder The number of position data bits is programmable as is the use of sin cos channels Use of...

Страница 15: ...lectrical cycle of the motor There are three of them U V W and they may be sourced by magnetic sensors in the motor or by encoders that have Hall tracks as part of the encoder disc They typically oper...

Страница 16: ...e external controllers that also need the motor feedback encoder signals because these now come from J8 the Control connector In addition to eliminating Y cabling where the motor feedback cable has to...

Страница 17: ...ARE CONNECTED TO MAINS POWER Fuse Fuse Earth Fuse Fuse Optional J3 REGEN REGEN Frame Ground U V W 1 4 5 2 3 4 3 2 1 Mot U Mot V Mot W Frame Ground J4 J1 J2 J8 24V BRAKE RTN Signal Ground Aout OUT2 OUT...

Страница 18: ...RCUITS ON J1 J2 J3 ARE CONNECTED TO MAINS POWER Fuse Fuse Earth Fuse Fuse Optional J3 REGEN REGEN Frame Ground U V W 1 4 5 2 3 4 3 2 1 Mot U Mot V Mot W Frame Ground J4 J1 J2 J8 24V BRAKE RTN Signal G...

Страница 19: ...AC MAINS 100 to 240 Vac 1 or 3 47 to 63 Hz L3 L2 L1 Fuse 1 H N LINE FILTER BRUSHLESS MOTOR DANGER HIGH VOLTAGE CIRCUITS ON J1 J2 J3 ARE CONNECTED TO MAINS POWER Fuse Fuse Earth Fuse Fuse Optional J3...

Страница 20: ...nd XPL 230 40 R models AWG 14 600V for XPL 230 18 R Shielded cable required for CE compliance J2 Cable Connector Wago 51118008 or 721 104 026 047 RN01 0000 Euro style 5 0 mm pluggable female terminal...

Страница 21: ...rame Gnd 10 Enc B1 19 Sin1 2 Hall U 11 Enc B1 20 Cos1 3 Hall V 12 Enc A1 21 Cos1 4 Hall W 13 Enc A1 22 Index1 5 Signal Gnd 14 Enc S1 23 Index1 6 5 Vdc Out 15 Enc S1 24 IN15 ENCFLT 7 AIN3 Motemp 16 Sig...

Страница 22: ...30 40 R models AWG 14 600V for XPL 230 18 R Shielded cable required for CE compliance J2 Cable Connector Wago 51118008 or 721 104 026 047 RN01 0000 Euro style 5 0 mm pluggable female terminal block Ca...

Страница 23: ...c B1 19 Sin1 S3 2 Hall U 11 Enc B1 20 Cos1 S4 3 Hall V 12 Enc A1 21 Cos1 S2 4 Hall W 13 Enc A1 22 Ref R2 5 Signal Gnd 14 Enc S1 23 Ref R1 6 5 Vdc Out 15 Enc S1 24 IN15 ENCFLT 7 AIN3 Motemp 16 Signal G...

Страница 24: ...e Because of their smaller wire gauge these should not be used as part of a safety ground system Motor cases can be safety grounded either at the motor by earthing the frame or by a grounding conducto...

Страница 25: ...ive remains at earth potential and eliminating a shock hazard that could occur of the chassis were allowed to float to the potential of the mains While this connection keeps the heatplate at earth pot...

Страница 26: ...o protective sheets blue on one side and clear on the other Both must be removed when the interface pad is installed STEPS TO INSTALL 1 Remove the blue protective sheet from one side of the pad and pl...

Страница 27: ...7 6 5 4 3 2 1 Standard Heatsink Low Profile Heatsink w fan Low Profile Heatsink or no Heatsink w fan Standard Heatsink w fan 5 1 2 3 4 No Heatsink Mains 240 Vac Continuous Output Current Adc Ambient...

Страница 28: ...above Norcomp 979 015 020R121 CME 2 J5 CME 2 Drive Configuration Software CD ROM SER CK RS 232 Cable Kit Heatsink Kits for Field Installation Optional XPL HL Heatsink Kit Low Profile 1 Heatsink low p...

Отзывы: