Chapter 7 Modbus mapping table
68
400153(0098)
CH1 Input deviation
Input deviation
correction
-999~999
Bit
0
400154(0099)
CH1 Input digital
filtering
Input digital
filtering
0.1~120.0
Secon
d
0.1
400155(009A)
CH1 SV Lower
limit
SV Lower limit
set value
Input lower limit range
~ SV upper limit - 1 bit
℃
/
℉
-200
400156(009B)
CH1 SV Upper
limit
SV Upper limit
set value
SV lower limit +1 bit
~Input upper limit
range
℃
/
℉
1350
400157(009C)
CH1 Operating
mode
Control output
mode of operation
0
:
Heating
1
:
Cooling
2
:
Heating & Cooling
-
0
400158(009D)
CH1 Control mode
Control
temperature mode
Standard control mode
0: PID
1: ONOFF
-
0
Heating & Cooling
control mode
0: PID-PID
1: PID-ONOFF
2: ONOFF-PID
3: ONOFF-ONOFF
-
0
400159(009E)
CH1 Auto-tuning
type
Auto-tuning type
0: TUN1
1: TUN2
-
TUN1
400160(009F)
CH1 Heating control
cycle
Heating control
cycle
0.1~120.0
Sec.
20.0(RY)
2.0(SSR)
400161(00A0)
CH1 Cooling control
cycle
Cooling control
cycle
0.1~120.0
Sec.
20.0(RY)
2.0(SSR)
40162(00A1)
~400200(00C7)
CH1 Reserved
401151(047E)
~ 401200(04AF)
CH2 parameter - same as above CH1
402151(0866)
~ 402200(0897)
CH3 parameter - same as above CH1
403151(0C4E)
~403200(0C7F)
CH4 parameter - same as above CH1