Chapter 4 Parameter settings and functions
47
4.5.2 Run/Stop Settings
◆
In the operation mode, the control output can be forced to run or stop.
◆
The control output stops after the STOP command is sent.
◆
Control the run/stop function by setting the digital input terminals (DI-1, DI-2).
When the RUN/STOP function is set to the stop state, the STOP
status remains valid even if the power is turned off again.
Displays the current control output operation amount (Stop.MV)
when the stop function is in effect, and keeps
When power is restored after stopping, the initial operation amount
is also the maximum operation amount.
Re-powering after RUN/STOP setting is still valid
Control output stop
When the control output is stopped, select between 0.0 (OFF) and 100.0 (ON) under
ON/OFF control.
Under PID control, the control output operation can be selected between 0.0 ~ 100.0.
Paramet
er
group
Associated
parameter
Param
eter
Setting range
Factory
default
Unit
Communica
tion address
Master
control
Output
Features
Heati
ng,
Cooli
ng
PID
CH1
stop
Operati
on
volume
0.0 ~ 100.0
0.0
%
400205(00CCH)
ON/OFF
0.0(OFF) ~ 100.0(ON)
Heati
ng&
Cooli
ng
PID
-100.0(Cooling) ~
100.0(heating)
0.0
ON/OFF
-100.0(Cooling ON)
/0.0(OFF) /
100.0(heating ON)
When set to STOP mode, ON/OFF control and PID control ignore
the set operation amount
4.5.3 Multi-segment SV
The multi-segment SV function allows the user to set multiple SV values and save them to
the SV0 ~ SV3 parameters. The desired SV value can be selected via the external digital
input (DI-1, DI-2) terminals.
Supports up to 4 SV values, which can be set individually.
Number of multi-segment SVs
The multi-segment SV value can be set according to the number of control objects.