Chapter 7 Modbus mapping table
67
400109(006C)
CH1 Manual reset
Manual reset in
proportional
control mode
0.0~100.0
%
50.0
400110(006D)
CH1 Heating hysteresis
Heating
hysteresis
1~100(H)
0.1~100.0(L)
Bit
2
400111(006E)
CH1 Heating deviation
Heating deviation
0~100(H)
0.0~100.0(L)
Bit
0
400112(006F)
CH1 Cooling hysteresis
value
Cooling
hysteresis value
1~100(H)
0.1~100.0(L)
Bit
2
400113(0070)
CH1 Refrigeration
deviation
Refrigeration
deviation
0~100(H)
0.0~100.0(L)
Bit
0
400114(0071)
CH1 MV Lower limit
MV Lower limit
set value
0.0 ~ MV upper
limit-0.1
(normal control)
-100.0 ~ 0
(Heating & Cooling
Control)
%
0.0
-100
400115(0072)
CH1 MV Upper limit
MV Upper limit
set value
MV Lower limit+
0.1~100.0
0~100
%
100
400116(0073)
CH1 Rising slope
Rising slope set
0~9999
-
0
400117(0074)
CH1 Falling slope
Falling slope set
0~9999
-
0
400118(0075)
CH1 slope time
Slope time unit
0:second 1
:
minute
2
:
hour
-
minute
400119(0076)
~400150(0095)
CH1 Reserved
401101(044C)
~401150(047D)
CH2 parameter - same as above CH1
402101(0834)
~402150(0865)
CH3 parameter - same as above CH1
403101(0C 1C)
~403150(0C4D)
CH4 parameter - same as above CH1
7.5.4 Initial setting function (Func: 03/06/16, RW: R/W)
NO(address)
Parameter
Description
Determination area
Unit
Factory
default
400151(0096)
CH1 input type
Input type
0: K(CA).H
~22: DPt100.L
-
K(CA).H
400152(0097)
CH1 unit
Temperature unit
of the sensor
0:
℃
1:
℉
-
℃