Chapter 4 Parameter settings and functions
29
4.1.2 Input type setting
This product supports a variety of sensors, users can choose thermocouple or
thermal resistance according to demand.
Different sensors can be used for each individual channel. Example): CH1 input type
= KCA.H, CH2 input type = JIC.H
Parameter
group
Parameter
Setting
range
Factory
default
Unit
Com
address
Initial set
function
CH1 Input type
Refer
to4.1.1
K(CA).H
−
400151(0096H)
When input type is changed, the upper and lower input range will automatically change to the
selected sensor input range, reset these parameters (SV, multi-segment SV setting,
SV-0~SV-3 and input deviation correction are initialized) to ensure that the measurement
environment remains unchanged.
If the measured range is above or below the input range, HHHH (above), LLLL (lower)
will be displayed, and OPEN will be displayed when the sensor is not connected or
disconnected.
4.1.3 Input sensor temperature unit setting
When the input sensor type is set, the temperature unit can be set according to the
actual demand.
Parameter group
Parameter
Setting range
Factory
default
Unit
Com
address
Initial set function CH1 Temp unit
℃
/
℉
℃
-
400152(0097H)
When the temperature unit is changed, the input type remains
the same, but SV, multi-segment SV setting, SV-0~SV-3, SV
upper/lower limit and input deviation correction are initialized.