Chapter 4 Parameter settings and functions
37
※
When the power is turned back on after the power is turned off, the operation amount is
controlled to output the value before the power is turned off.
Initial operation amount during manual control
If the manual operation amount is set to PR.MV (manual preset MV), the initial MV can
be manually modified.
Parameter
Group
Associated
parameter
Parameter
Setting range Factory
default
Unit
Com address
Master contr
ol output fun
ction
Heating, cooling, PID
CH1 Manual operation
Initial operation
0.0 ~ 100.0
0.0
%
400203(00CAH)
Heating&cooling,PID
-100.0 (Cooling) ~
0.0
~ 100.0 (Heating)
0.0
0.1~ -100.0When heating and cooling control, the heating
operation amount is set from
0.1 to 100.0, and the cooling operation amount is set from
0.1 to -100.0.