Chapter 7 Modbus mapping table
66
SV code
code optional
2: SV-2
3: SV-3
400053(0034)
CH1 SV-0 set value
SV-0 set value
SV Lower limit
~SV Upper limit
℃
/
℉
0
400054(0035)
CH1 SV-1 set value
SV-1 set value
SV Lower limit
~SV Upper limit
℃
/
℉
0
400055(0036)
CH1 SV-2 set value
SV-2 set value
SV Lower limit
~SV Upper limit
℃
/
℉
0
400056(0037)
CH1 SV-3 set value
SV-3 set value
SV Lower limit
~SV Upper limit
℃
/
℉
0
400057(0038)
~400100(0063)
CH1 Reserved
401051(041A)
~401100(044B)
CH2 parameter - same as above CH1
402051(0802)
~402100(0833)
CH3 parameter - same as above CH1
403051(0BEA)~
403100(0C1B)
CH4 parameter - same as above CH1
7.5.3 Master output function (Func: 03/06/16, RW: R/W)
NO(address)
Parameter
Description
Determination area
Unit
Factory
default
400101(0064)
CH1Auto-tuning
Auto-tuning
execution/stop
0
:
OFF
1
:
ON
-
OFF
400102(0065)
CH1
Heating-proportional
zone
Heating
proportional zone
0.1~999.9
℃
10
400103(0066)
CH1 Cooling-proportional
Cooling
proportional zone
0.1~999.9
℃
10
400104(0067)
CH1Heating-integration
time
Heating
integration time
0~9999
Secon
d
0
400105(0068)
CH1Cooling –integration
time
Cooling
integration time
0~9999
Secon
d
0
400106(0069)
CH1 Heating-derivative
time
Heating derivative
time
0~9999
Secon
d
0
400107(006A)
CH1 Cooling-derivative
Cooling derivative
time
0~9999
Secon
d
0
400108(006B)
CH1 Dead zone
Dead zone that
occurs in heating
& cooling control
mode
-P BAND~ +P BAND
-999.9 ~ 999.9
Bit
0.0
0