Rev. d 01/1 27
DMP052E
Setting - Analogue output 1 / 0-10Volt
P A 1
L o o p
Push
Set
key for at least 10 seconds to enter level 2, push
Up
key and select
P A 1
menu.
Push
Set
key to select the parameter to be modified. The parameter value blinks showing the edit
status: push the
Up
and
Down
keys to change values. Once the desired values are modified, push
the
Set
or
Esc
keys to exit.
Setting - Analogue output 2 / 0-10Volt
P A 2
L o o p
Push
Set
key for at least 10 seconds to enter level 2, push
Up
key and select
P A 2
menu.
Push
Set
key to select the parameter to be modified. The parameter value blinks showing the edit
status: push the
Up
and
Down
keys to change values. Once the desired values are modified, push
the
Set
or
Esc
keys to exit.
Visible only with 1, 2 and 4 operating modes (coP only if SC compensation sensor if present)
Operating mode selection
Enable from time schedule (if present) or permanent enable
P+I control enable
o P
A b o
i n t
Compensated or remote temperatures Set-point enable
c o P
Loop enable from D.i.1 switch
Loop enable from D.i.2 switch
A E 1
A E 2
Visible only with 1, 2 and 4 operating modes
Visible only with 1,3,4 operating modes, if Sh humidity sensor is present
Operating mode selection
Enable from Time schedule (if available) or permanent enable
P+I control enable
o P
A b o
i n t
Compensated or remote Set-point enable
Humidification minimum limit enable
Humidification max limit enable
c o P
L L H
L H H
Visi
Loop enable from D.i.1 switch
Loop enable from D.i.2 switch
A E 1
A E 2
Visible only with 1, 2, 4 operating modes
Visible only with 2, 3, 4 operating modes, if Sh humidity sensor is present
Visible only if SC compensation sensor is present
Содержание W500H
Страница 30: ...Rev d 01 1 30 DMP052E MENU DIAGRAM...