Rev. d 01/1 23
DMP052E
Parameter Loop
P A 2
- Mode A3
Push
Set
key to select the parameter to be modified. The parameter value blinks showing the edit
status: push the
Up
and
Down
keys to change values. Once the desired values are modified, push
the
Set
or
Esc
keys to exit.
Parameter Loop
P d 2
- Mode A1
Push
Set
key to select the parameter to be modified. The parameter value blinks showing the edit
status: push the
Up
and
Down
keys to change values. Once the desired values are modified, push
the
Set
or
Esc
keys to exit.
Humidification operating Set-point (read-only)
Minimum Set-point of humidification compensation
Minimum temperature of humidification compensation
S o H
S c 1
t c 1
Maximum Set-point of humidification compensation
Maximum temperature of humidification compensation
Humidification Proportional Band
S c 2
t c 2
b P H
Visible only with compensation on (coP parameter = On )
Humidification operating Set-point (read-only)
S t H
Visible only with compensation off (coP parameter = Off )
Enthalpy Set-point of Winter temperature
Enthalpy Set-point of Summer temperature
Enthalpy temperature proportional Band with upper inside Enthalpy
S t i
S t E
b E i
Enthalpy Set-point of Winter humidity
Enthalpy Set-point of Summer humidity
Enthalpy temperature proportional Band with upper outside Enthalpy
S H i
S H E
b E E
Minimum opening limit
L L A
Visible only with presence of signal from outside humidity sensor
Enthalpy humidity proportional band
b P H