background image

Series 965

User's Manual

0600-0003-0000 Rev. C
July 1998

Supersedes: 0600-0003-0000 Rev. B

$10.00

Made in the U.S.A.

Printed on Recycled Paper

Watlow Controls, 1241 Bundy Blvd., P.O. Box 5580, Winona, MN  55987-5580, Phone:  507/454-5300, Fax:  507/452-4507

Watlow Controls

1/16 DIN

Microprocessor-Based

Auto-tuning Control

Registered Company

 

Winona, Minnesota  USA

 

ISO 9001

96

TOTAL

3 Year Warranty

CUSTOMER

SATISFACTION

Содержание 965 Series

Страница 1: ...n the U S A Printed on Recycled Paper Watlow Controls 1241 Bundy Blvd P O Box 5580 Winona MN 55987 5580 Phone 507 454 5300 Fax 507 452 4507 WatlowControls 1 16 DIN Microprocessor Based Auto tuning Con...

Страница 2: ...tion for each step of the setup to verify that your selections are consistent with your applications If the problem persists after checking all the steps call for technical assistance Watlow Controls...

Страница 3: ...d Returns 38 Specifications 39 Model Number Information 40 Declaration of Conformity 41 Quick Reference Figures Tables Page Figure Item 4 Series 965 Input Output Overview 1 5 Multiple Panel Cutout Dim...

Страница 4: ...er the HSC parameter Special 965 features include the NEMA 4X rating dual four digit displays in either red or green optional low volt power supply auto tuning for both heat and cool outputs ramp to s...

Страница 5: ...rounded side of the external case gasket is facing the panel surface Check to see that the gasket is not twisted and is seated within the case bezel flush with the panel Place the case in the cutout y...

Страница 6: ...rmly against the back of the panel getting it as tight as possible Make sure you cannot move the case within the cutout if you can you do not have a NEMA 4X seal Now let s make sure we have a tight se...

Страница 7: ...and compare your model number to those shown here and also the model number breakdown in the Appendix of this manual All outputs are referenced to a de energized state The final wiring figure is a ty...

Страница 8: ...tion in your process or system where it reads an average temperature Put the sensor as near as possible to the material or space you want to control Air flow past this sensor should be moderate The se...

Страница 9: ...hen using a 2 wire RTD That resistance when added to the RTD element resis tance will result in erroneous input to the instrument To overcome this prob lem use a 3 wire RTD sensor which compensates fo...

Страница 10: ...65A 3 F 00 NOTE Switching inductive loads relay coils solenoids etc with the mechanical relay switched dc or solid state relay output options requires using an R C suppressor Watlow carries the R C su...

Страница 11: ...echanical Relay Wiring Figure 18 0 5 Amp Solid state Relay Without Contact Suppres sion Wiring External Load 7 SS2 SS2 1 Fuse L1 L2 Custommer Supplied Quencharc Customer Supplied Quencharc NOTE Output...

Страница 12: ...6 Not Used 7 Not Used 8 Not Used 9 DC 1 10 DC 1 11 L1 12 L2 1 120V VAC L1 L2 2 3 5 4 5 1 2 1 2 3 11 18 12 13 14 15 2 1CR 16 High Temperature Light 1 2 3 4 8 9 10 11 12 R SSR 240 10A DC1 DC Input Soli...

Страница 13: ...cent power is in the lower dis play Up arrow Down arrow Keys When pressed simultaneously for three seconds the Setup Menu appears displaying the LOC parameter Continue to press the Up arrow Down arrow...

Страница 14: ...efaults Changing the dFL prompt will set parameters to their factory default Document all current parameter settings first See Appendix 2 in the calibration section to change this parameter How to Set...

Страница 15: ...the Setup Menu all outputs are off Entering the Setup Menu The Setup Menu displays the parameters that configure the Series 965 s features to your application Enter the Setup Menu by pressing the Up...

Страница 16: ...oint is not adjustable in this level of lock out Manual operation is not permitted Bumpless transfer is defeated and outputs are disabled on sensor break Input Selects the sensor input type The intern...

Страница 17: ...19 for the Pb1 parameter Range 1 to 9999 0 1 to 999 9 0 01 to 99 99 1 to 5555 0 1 to 555 5 0 01 to 55 5 Default 3 0 3 0 03 2 0 2 0 02 Latching Selects whether the alarm is latching or non latching La...

Страница 18: ...to set point at all times OFF None rt 0 to 9999 100 hr rP OFF P L 0 to 100 100 dSP nor normal nor SEt Set Point lower only Pro Process upper only Table 2 Setup Menu Prompts and Descriptions Setup Menu...

Страница 19: ...0 Pb2 3 0 Reset Integral 1 2 An integral control action for Output 1 or 2 that auto matically eliminates offset or droop between set point and actual process temperature rE1 It1 Will not appear if Pb...

Страница 20: ...Units 25 F 0 99 9 F 0 55 5 C 0 99 9 Units 2 5 F 0 ON OFF control HSC switch diff If dFL SI 0 0 to 999 9 of span 3 rE1 0 00 to 9 99 repeats minute 0 00 repeats minute 0 00 No Reset Won t appear if Pb1...

Страница 21: ...he established set point The displayed set point remains unchanged Once the control finishes learning the system it returns to a standard PID control with the PID values automatically set as a result...

Страница 22: ...une the Series 965 to your thermal system The tuning settings here are for a broad spectrum of applications your system may have somewhat different requirements NOTE This is a slow procedure taking fr...

Страница 23: ...heating power The 965 allows a negative output value only with a Cl Cool selection on either Ot1 or Ot2 Con Auto matic operation provides closed loop on off or PID control When the operator transfers...

Страница 24: ...C as the high limit and 5 F 3 C as the low limit the high alarm trips at 107 F 41 6 C and the low alarm at 95 F 35 C If you change the set point to 130 F 54 4 C the alarms follow the set point and tr...

Страница 25: ...ange error only applies to RTD units The sensor input generated a value lower than the allowable signal range or the A D circuitry malfunctioned Enter a valid input Make sure the In parameter selected...

Страница 26: ...te at those levels on a power basis If output values were not stable the control outputs go to 0 power OFF If operator access is LOC 3 or 4 The control remains in auto operation and the outputs go off...

Страница 27: ...nes Cross other wiring at 90 angles whenever crossing lines is unavoidable Look at the system layout identify and locate electrical noise sources such as solenoids relay contacts motors etc Route the...

Страница 28: ...n uses L1 power lead to switch a load L2 return lead has the same switched signal and could couple unwanted noise into a control circuit Tie all ground terminals together with one lead usually green w...

Страница 29: ...n pressing the Up arrow Down arrow keys is ignored Calibration values won t be retained unless you are in the manual mode Press the Up arrow Down arrow key to change the upper display to YES Press MOD...

Страница 30: ...e upper display 3 MODE through the calibration menu until rSt appears in the lower display 4 Press the Up arrow key until YES appears in the upper display 5 Press the MODE key and the 965 advances to...

Страница 31: ...and connect the reference compensator or T C calibrator to Terminal 5 Negative and Terminal 3 Positive on the Series 965 terminal strip If using a compensator turn on and short the input wires If usin...

Страница 32: ...0mA Input Field Calibration Procedure Equipment Required Precision current source 0 20mA minimum range with 0 01mA resolution Setup and Calibration 1 Connect the AC line voltage L1 and L2 to the prope...

Страница 33: ...the multimeter should read approximately 4mA Allow at least 10 seconds to stabilize 6 Use the Up arrow Down arrow keys reverse acting to adjust the reading on the multimeter for 3 85mA 0 10mA Press th...

Страница 34: ...software to provide a data base DIN Deutsche Industrial Norms a widely recog nized German standard for engineering units Display capability In a digital indicating instru ment the entire possible span...

Страница 35: ...splaying resistance versus temperature characteristics Displays positive temperature coefficient Set point Intended value of the process variable Switching sensitivity In on off control the temperatur...

Страница 36: ...w Voltage Wiring 7 Lower Display 13 M M N Key 13 Manual Operation 13 23 Manual Tuning 22 Mechanical Relay 5 Amp Output 1 Wiring 10 Output 2 Wiring 11 MODE key 13 Model Number 39 N Noise Eliminating 28...

Страница 37: ...ber is on the outside of the carton and on all paperwork returned Ship on a Freight Prepaid basis 3 After we receive your return we will examine it and determine the cause for your action 4 In cases o...

Страница 38: ...ated resistive load 5A 30V dc 3 Switched dc signal provides a non isolated minimum turn on voltage of 3V dc into a minimum 500 load maximum on voltage not greater than 12V dc into an infinite load Sol...

Страница 39: ...age Power 0 100 240V ac nominal high voltage 1 12 24V ac nominal or 12 24V dc low voltage Display Upper Display Lower Display 00 Red Red RG Red Green GR Green Red GG Green Green Model No Series 965 Mo...

Страница 40: ...40 WATLOW Series 965 User s Manual Appendix Conformity Put Declaration of Conformity on this page...

Страница 41: ...ensor input generated a value lower than the allowable signal range or the A D circuitry malfunctioned Enter a valid input Make sure the In parameter matches your sensor and DIP switch setting Refer t...

Страница 42: ...iguration and model number Do not enter any values here make photocopies instead Setup Menu Parameters Value Range Factory Default Appears If Pb1 0 to 999 F 0 to 555 C 0 to 999 Units 25 F dFL US 0 to...

Страница 43: ...2 WATLOW Series 985 User s Manual Appendix Watlow Series 965 User s Manual Watlow Controls 1241 Bundy Blvd P O Box 5580 Winona MN 55987 5580 Phone 507 454 5300 Fax 507 452 4507...